| 2020-01-31 11:38:17 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19110659 |
| | 1/31/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A1.1.3 & M1.1.3: THE EXHAUST SHAFT CANNOT |
| | SERVE MULTIPLE EXHAUST DUCTS, PIPING, AND WIRING- |
| | SECTION 506.3.11 FBC M. IF THE INTENTION IS FOR ALL |
| | EXHAUST DUCT TO BE WRAPPED IN 2-HR FIRE RATED DUCT WRAP |
| | ENCLOSURES, PLEASE PLACE A NOTE ON THE PLAN |
| | ACCORDINGLY. PLEASE NOTE HOWEVER THAT THE PIZZA OVEN |
| | AND SOLID FUEL APPLIANCE MANUFACTURER'S MAY RECOMMEND |
| | UL LISTED AND LABELED EXHAUST DUCTS THAT MAY NOT BE |
| | RATED AS DUCT ENCLOSURES, AND MAY ALSO PROHIBIT DUCT |
| | WRAPPING- SEE SECTIONS 506.3.1.1 & 506.3.11.3. IT IS |
| | IMPORTANT TO GET THESE DETAILS STRAIGHT ON THE MAIN |
| | PERMIT PLANS NOW PRIOR TO REVIEW OF THE SEPARATE PERMIT |
| | PLANS FOR THE KITCHEN EXHAUST SYSTEMS. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SOLID |
| | FUEL COOKING APPLIANCE- SECTION 917.1 FBC M. UL 2162 |
| | LISTING AND LABELING REQUIRED. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OUTDOOR |
| | TIKI TORCHES, AND THE GAS FIREPLACE- SECTIONS 626 AND |
| | 605 FBC FG. THESE SUBMITTALS WERE LEFT OUT OF THE |
| | SUBMITTAL PACKAGE. |
| | |
| | 4) SHEETS M1.1.1, M1.1.2, M1.1.3: PLEASE ADD THE SOLID |
| | FUEL FIRED COOKING APPLIANCE TO THE LIST OF SEPARATELY |
| | PERMITTED ITEMS, AND INCLUDE COMBUSTION AIR |
| | CALCULATIONS- SECTION 701.1 FBC M. |
| | |
| | 5) SHEET M1.1.3: PLEASE PLACE A TOP INDICATING THAT ALL |
| | ROOFTOP MECHANICAL EQUIPMENT AND APPLIANCES SHALL BE |
| | INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDED |
| | CLEARANCES, AND TO ALLOW ACCESS FOR SERVICE AND |
| | REPLACEMENT. |
| | |
| | A) RELOCATE FAN 2-B TO PROVIDE CLEARANCE TO THE RACK |
| | AND CU'S- SECTIONS 306.1 AND 506.3.13.3 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |