| 2019-12-23 12:49:16 | 1ST REVIEW 19110659 |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA BUILDING CODE PLUMBING 2017 6TH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P1.2.1 PLEASE EXPAND AND SEPARATE THE WATER AND |
| | GAS ISOMETRICS THEY ARE TO COMPACT TO DETERMINE CODE |
| | COMPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. P1.2.2 PLEASE EXPAND THE SANITARY ISOMETRIC |
| | DRAWING SOME OF THE PIPES APPEAR TO BE CONNECTING WHERE |
| | THEY CROSS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. PROVIDE BACK FLOW DEVISES ON ALL APPLIANCES |
| | CONNECTED TO THE WATER SYSTEM SUCH AS WATER FILTERS, |
| | ICE MACHINES COFFEE AND TEA MAKERS . PER FBC PL 608.3, |
| | 608.16.1,608.16.10 |
| | |
| | 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |