| 2019-12-24 12:17:14 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19110659 |
| | 12/24/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN |
| | EXHAUST HOODS, PIZZA OVENS, FIRE SUPPRESSION SYSTEMS, |
| | AND THE WALK-IN COOLER AND FREEZER. PLEASE PLACE A BOLD |
| | NOTE ON THE PLAN- SECTION 107.2.1 WPB. |
| | |
| | 2) PLEASE INDICATE HOW COMBUSTION AIR WILL BE SUPPLIED |
| | TO THE GAS AND SOLID FUEL FIRED COOKING APPLIANCES, AND |
| | THE PIZZA OVENS AND PROVIDE CALCULATIONS- SEE SECTION |
| | 304.1 FBC FG. PLEASE NOTE THAT PRODUCT SPECIFICATIONS |
| | FOR ALL THE APPLIANCES SHALL BE SUBMITTED IN THE SECOND |
| | REVIEW CYCLE OR MAY BE DEFERRED BY REQUEST. |
| | |
| | 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | OCCUPIED ROOMS AND SPACES- TABLE 403.3.1.1 FBC M. |
| | |
| | 4) PROVIDE ENGINEERING FOR IINSTALLATION OF ALL THE |
| | ROOFTOP MECHANICAL EQUIPMENT, APPLIANCES, AND DUCTWORK- |
| | SECTION 301.15 FBC M. |
| | |
| | 5) COMMISSIONING OF THE MECHANICAL AND SERVICE WATER |
| | HEATING SYSTEMS IS REQUIRED PER SECTION C408.2 FBC EC. |
| | SUBMIT A COMMISSIONING PLAN AS OUTLINED IN SECTION |
| | C408.2.1 AND DESCRIBED IN SECTIONS C403.2.2- |
| | C408.2.3.3. PLEASE NOTE THAT A COPY OF THE |
| | COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT |
| | FINAL INSPECTION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |