| Date |
Text |
| 2019-12-03 16:27:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LS 1.1 - THERE IS AN INDICATION OF AN EXIT |
| | LEADING THRU THE KITCHEN TO A FENCED IN AREA THAT IS |
| | NOT A PUBLIC WAY. |
| | |
| | THERE IS A SLIDING GATE; HOWEVER, THERE IS NO EXIT SIGN |
| | AT THE GATE OF EXIT HARDWARE MEETING THE REQUIRMENT OF |
| | NFPA 101, CH 7 MEANS OF EGRESS. |
| | |
| | 7.2.1 DOOR OPENINGS. |
| | 7.2.1.1 GENERAL. |
| | 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL |
| | CONFORM TO |
| | THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE |
| | SPECIAL |
| | REQUIREMENTS OF 7.2.1. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | |
| | 7.2.1.14 SPECIAL-PURPOSE HORIZONTALLY SLIDING ACCORDION |
| | OR |
| | FOLDING DOOR ASSEMBLIES. SPECIAL-PURPOSE HORIZONTALLY |
| | SLIDING |
| | ACCORDION OR FOLDING DOOR ASSEMBLIES SHALL BE PERMITTED |
| | IN MEANS |
| | OF EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA |
| | ARE MET: |
| | (1) THE DOOR LEAF IS READILY OPERABLE FROM EITHER SIDE |
| | WITHOUT |
| | SPECIAL KNOWLEDGE OR EFFORT. |
| | (2) THE FORCE THAT, WHEN APPLIED TO THE OPERATING |
| | DEVICE IN THE |
| | DIRECTION OF EGRESS, IS REQUIRED TO OPERATE THE DOOR |
| | LEAF IS NOT |
| | MORE THAN 15 LBF (67 N). |
| | (3) THE FORCE REQUIRED TO OPERATE THE DOOR LEAF IN THE |
| | DIRECTION OF |
| | TRAVEL IS NOT MORE THAN 30 LBF (133 N) TO SET THE LEAF |
| | IN |
| | MOTION AND IS NOT MORE THAN 15 LBF (67 N) TO CLOSE THE |
| | LEAF OR |
| | OPEN IT TO THE MINIMUM REQUIRED WIDTH. |
| | (4) THE DOOR LEAF IS OPERABLE USING A FORCE OF NOT MORE |
| | THAN 50 |
| | LBF (222 N) WHEN A FORCE OF 250 LBF (1100 N) IS APPLIED |
| | PERPENDICULARLY TO THE LEAF ADJACENT TO THE OPERATING |
| | DEVICE, |
| | UNLESS THE DOOR OPENING IS AN EXISTING SPECIAL-PURPOSE |
| | HORIZONTAL-SLIDING ACCORDION OR FOLDING EXIT ACCESS |
| | DOOR |
| | ASSEMBLY SERVING AN AREA WITH AN OCCUPANT LOAD OF FEWER |
| | THAN 50. |
| | (5) THE DOOR ASSEMBLY COMPLIES WITH THE FIRE PROTECTION |
| | RATING, |
| | IF REQUIRED, AND, WHERE RATED, IS SELF-CLOSING OR |
| | AUTOMATIC CLOSING |
| | BY MEANS OF SMOKE DETECTION IN ACCORDANCE WITH |
| | 7.2.1.8 AND IS INSTALLED IN ACCORDANCE WITH NFPA 80, |
| | STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES. |
| | (6) THE DOOR, IF POWER OPERATED, SHALL BE CAPABLE OF |
| | BEING |
| | OPERATED MANUALLY IN THE EVENT OF POWER FAILURE. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| | CODE. |
| | |
| | |
| | 2) SHEET LS 1.1 - THERE ARE INDICATION OF A OUTDOOR |
| | SEATING PLAN; HOWEVER, THERE APPEARS TO BE ENCROACHMENT |
| | INTO THE EGRESS PATH LEADING TO EXITS. |
| | |
| | PER NFPA 101, CH 12, NEW ASSEMLY OCCUOPANCIES |
| | |
| | 12.2.5.7* AISLE ACCESSWAYS SERVING SEATING AT TABLES. |
| | 12.2.5.7.1 THE REQUIRED CLEAR WIDTH OF AN AISLE |
| | ACCESSWAY SHALL BE |
| | NOT LESS THAN 12 IN. (305 MM) WHERE MEASURED IN |
| | ACCORDANCE WITH |
| | 12.2.5.7.3 AND SHALL BE INCREASED AS A FUNCTION OF |
| | LENGTH IN |
| | ACCORDANCE WITH 12.2.5.7.4, UNLESS OTHERWISE PERMITTED |
| | BY |
| | 12.2.5.7.2. |
| | 12.2.5.7.2* IF USED BY NOT MORE THAN FOUR PERSONS, NO |
| | MINIMUM |
| | CLEAR WIDTH SHALL BE REQUIRED FOR THE PORTION OF AN |
| | AISLE ACCESSWAY |
| | HAVING A LENGTH NOT EXCEEDING 6 FT (1830 MM) AND |
| | LOCATED FARTHEST |
| | FROM AN AISLE. |
| | 12.2.5.7.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A |
| | TABLE AND |
| | AN AISLE ACCESSWAY OR AISLE, THE MEASUREMENT OF |
| | REQUIRED CLEAR |
| | WIDTH OF THE AISLE ACCESSWAY OR AISLE SHALL BE MADE TO |
| | A LINE 19 IN. |
| | (485 MM), MEASURED PERPENDICULARLY TO THE EDGE OF THE |
| | TABLE, |
| | AWAY FROM THE EDGE OF SAID TABLE. |
| | 12.2.5.7.4* THE MINIMUM REQUIRED CLEAR WIDTH OF AN |
| | AISLE |
| | ACCESSWAY, MEASURED IN ACCORDANCE WITH 12.2.5.4.8 AND |
| | 12.2.5.7.3, |
| | SHALL BE INCREASED BEYOND THE 12 IN. (305 MM) |
| | REQUIREMENT OF |
| | 12.2.5.7.1 BY ? IN. (13 MM) FOR EACH ADDITIONAL 12 IN. |
| | (305 MM) |
| | OR FRACTION THEREOF BEYOND 12 FT (3660 MM) OF AISLE |
| | ACCESSWAY |
| | LENGTH, WHERE MEASURED FROM THE CENTER OF THE SEAT |
| | FARTHEST FROM |
| | AN AISLE. |
| | 12.2.5.7.5 THE PATH OF TRAVEL ALONG THE AISLE ACCESSWAY |
| | SHALL NOT |
| | EXCEED 36 FT (11 M) FROM ANY SEAT TO THE CLOSEST AISLE |
| | OR EGRESS |
| | DOORWAY. |
| | 12.2.5.8 AISLES SERVING SEATING AT TABLES. |
| | 12.2.5.8.1* AISLES THAT CONTAIN STEPS OR THAT ARE |
| | RAMPED, SUCH AS |
| | AISLES SERVING DINNER THEATER?STYLE CONFIGURATIONS, |
| | SHALL COMPLY |
| | WITH THE REQUIREMENTS OF 12.2.5.6. |
| | 12.2.5.8.2* THE WIDTH OF AISLES SERVING SEATING AT |
| | TABLES SHALL BE |
| | NOT LESS THAN 44 IN. (1120 MM) WHERE SERVING AN |
| | OCCUPANT LOAD |
| | EXCEEDING 50, AND 36 IN. (915 MM) WHERE SERVING AN |
| | OCCUPANT |
| | LOAD OF 50 OR FEWER. |
| | 12.2.5.8.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A |
| | TABLE AND |
| | AN AISLE, THE MEASUREMENT OF REQUIRED CLEAR WIDTH OF |
| | THE AISLE SHALL |
| | BE MADE TO A LINE 19 IN. (485 MM), MEASURED |
| | PERPENDICULARLY TO |
| | THE EDGE OF THE TABLE, AWAY FROM THE EDGE OF SAID |
| | TABLE. |
| | 12.2.5.9 APPROVAL OF LAYOUTS. |
| | 12.2.5.9.1 WHERE REQUIRED BY THE AUTHORITY HAVING |
| | JURISDICTION, |
| | PLANS DRAWN TO SCALE SHOWING THE ARRANGEMENT OF |
| | FURNISHINGS OR |
| | EQUIPMENT SHALL BE SUBMITTED TO THE AUTHORITY BY THE |
| | BUILDING |
| | OWNER, MANAGER, OR AUTHORIZED AGENT TO SUBSTANTIATE |
| | CONFORMANCE |
| | WITH THE PROVISIONS OF 12.2.5. |
| | 12.2.5.9.2 THE LAYOUT PLANS SHALL CONSTITUTE THE ONLY |
| | ACCEPTABLE |
| | ARRANGEMENT, UNLESS ONE OF THE FOLLOWING CRITERIA IS |
| | MET: |
| | (1) THE PLANS ARE REVISED. |
| | (2) ADDITIONAL PLANS ARE SUBMITTED AND APPROVED. |
| | (3) TEMPORARY DEVIATIONS FROM THE SPECIFICATIONS OF THE |
| | APPROVED PLANS ARE USED, PROVIDED THAT THE OCCUPANT |
| | LOAD IS |
| | NOT INCREASED AND THE INTENT OF 12.2.5.9 IS MAINTAINED. |
| | |
| | PLEASE PROVIDE DETAILED DIEMSIONS OF ALONG THE EGRESS |
| | PATH. |
| | |
| | |
| | 3) |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |