Plan Review Notes
Plan Review Notes For Permit 19110659
Permit Number 19110659
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-12-03 16:27:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 1.1 - THERE IS AN INDICATION OF AN EXIT
 LEADING THRU THE KITCHEN TO A FENCED IN AREA THAT IS
 NOT A PUBLIC WAY.
  
 THERE IS A SLIDING GATE; HOWEVER, THERE IS NO EXIT SIGN
 AT THE GATE OF EXIT HARDWARE MEETING THE REQUIRMENT OF
 NFPA 101, CH 7 MEANS OF EGRESS.
  
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO
 THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE
 SPECIAL
 REQUIREMENTS OF 7.2.1.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.14 SPECIAL-PURPOSE HORIZONTALLY SLIDING ACCORDION
 OR
 FOLDING DOOR ASSEMBLIES. SPECIAL-PURPOSE HORIZONTALLY
 SLIDING
 ACCORDION OR FOLDING DOOR ASSEMBLIES SHALL BE PERMITTED
 IN MEANS
 OF EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE DOOR LEAF IS READILY OPERABLE FROM EITHER SIDE
 WITHOUT
 SPECIAL KNOWLEDGE OR EFFORT.
 (2) THE FORCE THAT, WHEN APPLIED TO THE OPERATING
 DEVICE IN THE
 DIRECTION OF EGRESS, IS REQUIRED TO OPERATE THE DOOR
 LEAF IS NOT
 MORE THAN 15 LBF (67 N).
 (3) THE FORCE REQUIRED TO OPERATE THE DOOR LEAF IN THE
 DIRECTION OF
 TRAVEL IS NOT MORE THAN 30 LBF (133 N) TO SET THE LEAF
 IN
 MOTION AND IS NOT MORE THAN 15 LBF (67 N) TO CLOSE THE
 LEAF OR
 OPEN IT TO THE MINIMUM REQUIRED WIDTH.
 (4) THE DOOR LEAF IS OPERABLE USING A FORCE OF NOT MORE
 THAN 50
 LBF (222 N) WHEN A FORCE OF 250 LBF (1100 N) IS APPLIED
 PERPENDICULARLY TO THE LEAF ADJACENT TO THE OPERATING
 DEVICE,
 UNLESS THE DOOR OPENING IS AN EXISTING SPECIAL-PURPOSE
 HORIZONTAL-SLIDING ACCORDION OR FOLDING EXIT ACCESS
 DOOR
 ASSEMBLY SERVING AN AREA WITH AN OCCUPANT LOAD OF FEWER
 THAN 50.
 (5) THE DOOR ASSEMBLY COMPLIES WITH THE FIRE PROTECTION
 RATING,
 IF REQUIRED, AND, WHERE RATED, IS SELF-CLOSING OR
 AUTOMATIC CLOSING
 BY MEANS OF SMOKE DETECTION IN ACCORDANCE WITH
 7.2.1.8 AND IS INSTALLED IN ACCORDANCE WITH NFPA 80,
 STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES.
 (6) THE DOOR, IF POWER OPERATED, SHALL BE CAPABLE OF
 BEING
 OPERATED MANUALLY IN THE EVENT OF POWER FAILURE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 CODE.
  
  
 2) SHEET LS 1.1 - THERE ARE INDICATION OF A OUTDOOR
 SEATING PLAN; HOWEVER, THERE APPEARS TO BE ENCROACHMENT
 INTO THE EGRESS PATH LEADING TO EXITS.
  
 PER NFPA 101, CH 12, NEW ASSEMLY OCCUOPANCIES
  
 12.2.5.7* AISLE ACCESSWAYS SERVING SEATING AT TABLES.
 12.2.5.7.1 THE REQUIRED CLEAR WIDTH OF AN AISLE
 ACCESSWAY SHALL BE
 NOT LESS THAN 12 IN. (305 MM) WHERE MEASURED IN
 ACCORDANCE WITH
 12.2.5.7.3 AND SHALL BE INCREASED AS A FUNCTION OF
 LENGTH IN
 ACCORDANCE WITH 12.2.5.7.4, UNLESS OTHERWISE PERMITTED
 BY
 12.2.5.7.2.
 12.2.5.7.2* IF USED BY NOT MORE THAN FOUR PERSONS, NO
 MINIMUM
 CLEAR WIDTH SHALL BE REQUIRED FOR THE PORTION OF AN
 AISLE ACCESSWAY
 HAVING A LENGTH NOT EXCEEDING 6 FT (1830 MM) AND
 LOCATED FARTHEST
 FROM AN AISLE.
 12.2.5.7.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A
 TABLE AND
 AN AISLE ACCESSWAY OR AISLE, THE MEASUREMENT OF
 REQUIRED CLEAR
 WIDTH OF THE AISLE ACCESSWAY OR AISLE SHALL BE MADE TO
 A LINE 19 IN.
 (485 MM), MEASURED PERPENDICULARLY TO THE EDGE OF THE
 TABLE,
 AWAY FROM THE EDGE OF SAID TABLE.
 12.2.5.7.4* THE MINIMUM REQUIRED CLEAR WIDTH OF AN
 AISLE
 ACCESSWAY, MEASURED IN ACCORDANCE WITH 12.2.5.4.8 AND
 12.2.5.7.3,
 SHALL BE INCREASED BEYOND THE 12 IN. (305 MM)
 REQUIREMENT OF
 12.2.5.7.1 BY ? IN. (13 MM) FOR EACH ADDITIONAL 12 IN.
 (305 MM)
 OR FRACTION THEREOF BEYOND 12 FT (3660 MM) OF AISLE
 ACCESSWAY
 LENGTH, WHERE MEASURED FROM THE CENTER OF THE SEAT
 FARTHEST FROM
 AN AISLE.
 12.2.5.7.5 THE PATH OF TRAVEL ALONG THE AISLE ACCESSWAY
 SHALL NOT
 EXCEED 36 FT (11 M) FROM ANY SEAT TO THE CLOSEST AISLE
 OR EGRESS
 DOORWAY.
 12.2.5.8 AISLES SERVING SEATING AT TABLES.
 12.2.5.8.1* AISLES THAT CONTAIN STEPS OR THAT ARE
 RAMPED, SUCH AS
 AISLES SERVING DINNER THEATER?STYLE CONFIGURATIONS,
 SHALL COMPLY
 WITH THE REQUIREMENTS OF 12.2.5.6.
 12.2.5.8.2* THE WIDTH OF AISLES SERVING SEATING AT
 TABLES SHALL BE
 NOT LESS THAN 44 IN. (1120 MM) WHERE SERVING AN
 OCCUPANT LOAD
 EXCEEDING 50, AND 36 IN. (915 MM) WHERE SERVING AN
 OCCUPANT
 LOAD OF 50 OR FEWER.
 12.2.5.8.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A
 TABLE AND
 AN AISLE, THE MEASUREMENT OF REQUIRED CLEAR WIDTH OF
 THE AISLE SHALL
 BE MADE TO A LINE 19 IN. (485 MM), MEASURED
 PERPENDICULARLY TO
 THE EDGE OF THE TABLE, AWAY FROM THE EDGE OF SAID
 TABLE.
 12.2.5.9 APPROVAL OF LAYOUTS.
 12.2.5.9.1 WHERE REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION,
 PLANS DRAWN TO SCALE SHOWING THE ARRANGEMENT OF
 FURNISHINGS OR
 EQUIPMENT SHALL BE SUBMITTED TO THE AUTHORITY BY THE
 BUILDING
 OWNER, MANAGER, OR AUTHORIZED AGENT TO SUBSTANTIATE
 CONFORMANCE
 WITH THE PROVISIONS OF 12.2.5.
 12.2.5.9.2 THE LAYOUT PLANS SHALL CONSTITUTE THE ONLY
 ACCEPTABLE
 ARRANGEMENT, UNLESS ONE OF THE FOLLOWING CRITERIA IS
 MET:
 (1) THE PLANS ARE REVISED.
 (2) ADDITIONAL PLANS ARE SUBMITTED AND APPROVED.
 (3) TEMPORARY DEVIATIONS FROM THE SPECIFICATIONS OF THE
 APPROVED PLANS ARE USED, PROVIDED THAT THE OCCUPANT
 LOAD IS
 NOT INCREASED AND THE INTENT OF 12.2.5.9 IS MAINTAINED.
  
 PLEASE PROVIDE DETAILED DIEMSIONS OF ALONG THE EGRESS
 PATH.
  
  
 3)
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  