| Notes |
| Date |
Text |
| 2019-11-22 15:27:00 | 1) I AM QUESTIONING THE VALUATION OF THIS PROJECT. | | | SUBMIT DETAILED , QUANTITY ESTIMATES AND/OR A BONA FIDE | | | SIGNED CONTRACT FOR REVIEW. WPB AMEND. TO FBC SEC. | | | 109.3. | | | 2) INDICATE ON THE SITE PLAN IF ANY NEW PIPING WILL BE | | | REPLACED/INSTALLED OR ARE THE PUMPS CONNECTING TO | | | EXISTING PIPING. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) IF NEW PIPING IS BEING INSTALLED, SUBMIT PIPING | | | PLANS SHOWING THE PIPE AND PIPE SIZES, TYPE OF | | | SUPPORTS, SPACING OF SUPPORTS, ETC. WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | PUMPS.WPB AMEND. TO FBC SEC. 107.2.1. | | | 5) PART VII OF THE MANUAL - COMPLETE THE FRICTION LOSS | | | WORKSHEET TO ENSURE THE UNIT THAT IS BEING INSTALLED | | | HAS SUFFICIENT CAPACITY TO OPERATE RELIABLY IN THE | | | SPECIFIC INSTALLATION. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|