| 2020-05-28 12:26:50 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT 19110539 |
| | 5/28/20 |
| | |
| | CODES IN EFFECT: |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THIS IS THE 3RD REVIEW AND THE 1ST REVIEW COMMENTS |
| | LISTED BELOW HAVE STILL NOT BEEN ADDRESSED AND AGAIN NO |
| | NARRATIVE RESPONSE WAS PROVIDED. |
| | THE ENGINEER OF RECORD SHALL PROVIDE A WRITTEN RESPONSE |
| | TO THE COMMENTS, AND PROVIDE A SCOPE OF WORK OULTINE |
| | FOR PLUMBING AND ROOF DRAINAGE UNDER THIS PERMIT. THE |
| | SCOPE AND LIMITATIONS OF THE WORK SHALL BE CLEARLY |
| | NOTED ON THE PLAN AND CORRESPONDING DRAWINGS AND |
| | DETAILS SHALL BE PROVIDED- SECTION 107.2.1 WPB. |
| | |
| | 1. SHEET P200: ON ROOFS WHERE PONDING COULD OCCUR IF |
| | THE PRIMARY DRAIN IS CLOGGED A EMERGENCY OVERFLOW ROOF |
| | DRAIN IS REQUIRED. PER FBC PL 1108.1. |
| | |
| | 2.P200: PROVIDE SIZING CALCULATION FOR ALL NEW ROOF |
| | DRAINS . PER FBC PL 1106.2. |
| | |
| | 5. P200: SHOW STORM PIPING FOR STAIR WELLS. PER WPB |
| | AMEND TO FBC 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |