| Date |
Text |
| 2020-05-14 08:36:57 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT 19110539 |
| | 5/14/20 |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE 1ST REVIEW COMMENTS LISTED BELOW WERE NOT ADDRESSED |
| | ON THE RESUMBITTED PLANS, AND THERE WAS NO NARRATIVE |
| | RESPONSE PROVIDED. PLEASE COMPLY WITH THE COMMENTS. |
| | PLEASE NOTE IF THE ROOF DRAINAGE FOR THE PORTE COCHERE |
| | IS NOT TO BE INCLUDED IN THE THIS PERMIT SUBMITTAL, |
| | PROVIDE NOTES ON THE PLAN TO INDICATE THE LIMITATIONS |
| | OF THE PLUMBING AND ROOF DRAINAGE WORK UNDER THIS |
| | PERMIT. |
| | |
| | 1. SHEET P200: ON ROOFS WHERE PONDING COULD OCCUR IF |
| | THE PRIMARY DRAIN IS CLOGGED A EMERGENCY OVERFLOW ROOF |
| | DRAIN IS REQUIRED. PER FBC PL 1108.1 |
| | |
| | 2.P200: PROVIDE SIZING CALCULATION FOR ALL NEW ROOF |
| | DRAINS . PER FBC PL 1106.2 |
| | |
| | 5. P200: SHOW STORM PIPING FOR STAIR WELLS. PER WPB |
| | AMEND TO FBC 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |
| | |