2020-05-28 12:28:583RD REVIEW FBC-2017 FUEL GAS
 PERMIT 19110539
 5/28/20
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 2ND REVIEW WERE NOT COMPLETED
 ADDRESSED.
  
 1) SHEET P200- GAS PIPING LAYOUT AND RISER DRAWINGS:
 A) TOTAL LENGTH OF THE RUN, AND THE TYPE OF 1-1/4"
 PIPING TO THE NEW FIRE PIT NOT SHOWN- SECTIONS 402.4.1,
 402.4.2 FBC FG.
  
 2) THE REQUESTED MANUFACTURER'S SPECIFICATIONS FOR THE
 FIRE PIT WERE NOT SUBMITTED- SECTIONS 601.1 AND 636.1
 FBC FG.
  
 3) P200: AS NOTED ABOVE THE TYPE OF UNDERSLAB PIPING
 FROM THE BUILDING TO THE FIRE PIT NEEDS TO BE
 IDENTIFIED AND THE BURIAL DEPTH BELOW GRADE INDICATED-
 SECTION 404.12 AND 404.12.1 FBC FG. IF METALLIC PIPING
 IS TO BE USED IN MUST BE PROTECTED AGAINST CORROSION IN
 ACCORDANCE WITH SECTION 404.11. PLEASE NOTE THAT PE
 PIPE MAY BE USED UNDERSLAB PER SECTION 404.17.3 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  