| 2020-05-28 12:28:58 | 3RD REVIEW FBC-2017 FUEL GAS |
| | PERMIT 19110539 |
| | 5/28/20 |
| | |
| | CODES IN EFFECT: |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENTS FROM THE 2ND REVIEW WERE NOT COMPLETED |
| | ADDRESSED. |
| | |
| | 1) SHEET P200- GAS PIPING LAYOUT AND RISER DRAWINGS: |
| | A) TOTAL LENGTH OF THE RUN, AND THE TYPE OF 1-1/4" |
| | PIPING TO THE NEW FIRE PIT NOT SHOWN- SECTIONS 402.4.1, |
| | 402.4.2 FBC FG. |
| | |
| | 2) THE REQUESTED MANUFACTURER'S SPECIFICATIONS FOR THE |
| | FIRE PIT WERE NOT SUBMITTED- SECTIONS 601.1 AND 636.1 |
| | FBC FG. |
| | |
| | 3) P200: AS NOTED ABOVE THE TYPE OF UNDERSLAB PIPING |
| | FROM THE BUILDING TO THE FIRE PIT NEEDS TO BE |
| | IDENTIFIED AND THE BURIAL DEPTH BELOW GRADE INDICATED- |
| | SECTION 404.12 AND 404.12.1 FBC FG. IF METALLIC PIPING |
| | IS TO BE USED IN MUST BE PROTECTED AGAINST CORROSION IN |
| | ACCORDANCE WITH SECTION 404.11. PLEASE NOTE THAT PE |
| | PIPE MAY BE USED UNDERSLAB PER SECTION 404.17.3 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |