Plan Review Notes
Plan Review Notes For Permit 19110539
Permit Number 19110539
Review Stop B
Sequence Number 3
Notes
Date Text
2020-05-13 08:51:492017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110539 (FA?ADE RENOVATIONS & NEW
 COMPONENTS AND CLADDING)
 ADD: 600 NORTHPOINT PARKWAY
 CONT:TBD/ TO BE DETERMINED
 TEL: ?????? CONTACT: ASHLEE CALLAHAN
 E-MAIL:[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 PERMITS ASSOCIATED WITH THE OVERALL PROJECT.
 19110539 FA?ADE RENOVATIONS & NEW CLADDING
 ???????? PORTE COCHERE
 19120240 INT. REMODEL OF GUEST ROOMS
 19120241 INT. REMODEL OF CORRIDORS & PUBLIC SPACES.
  
 3RD REVIEW
 DATE: MAY MON. - WED11-13/ 2020
 ACTION: DENIED
  
 **** COMMENT # 6 DENIED. NOTE MONDAY I REACHED OUT TO
 THE ARCHITECT CR ARCHITECTS TO SEE ABOUT RED LINING
 DRAWINGS. I ASKED TO SPEAK TO THE ARCHITECT DAVID
 ARENDS, THEY PUT ME THROUGH TO ERWIND (#2108) AND
 RECEIVED HIS VOICE MAIL. I HAVE CALLED THIS NUMBER
 TWICE AND RECEIVED NO RETURN TELEPHONE CALLS, I AM
 WORKING FROM HOME AND EVEN LEFT MY CELL PHONE NUMBER
 561-718-9724 TO GET BACK IN TOUCH WITH ME.
  
 1) PROVISO: PORT COCHERE TO BE UNDER SEPARATE PERMIT
 AND ASSOCIATED FEES. APPLY SEPARATELY NOT UNDER THIS
 PERMIT.
  
 2) PROVISO: THE REPLACEMENT PORTE COCHERE IS TO BE
 PROVIDED BY THE OWNER AND INSTALLED BY OTHERS (ANOTHER
 CONTRACTOR
  
 3-4) PROVISO: THE DESIGNER OF RECORD HAS STATED THAT
 THE PORTE COCHERE WILL BE UNDER SEPARATE PERMIT,
 REVIEWS AND ASSOCIATED FEES. TO DATE NO PERMIT HAS BEEN
 APPLIED FOR.
  
 5) PROVISO: THE NEW REPLACEMENT PORTICO WILL REQUIRE
 FIRE SPRINKLERS TO BE CONSIDERED PART OF THE MAIN
 BUILDING BEING FIRE SPRINKLERED ALREADY.
  
  
 6) 3RD REQUEST, SEMI-COMPLIED. SHEET G-100. THE
 STANDARD PARKING DETAIL AS SHOWN SHOWS AN OVERALL WIDTH
 OF 16 INCHES WIDE WITH 2 4 INCH STRIPES AND A 8 INCHES
 BETWEEN THE STRIPES. THE CITY STANDARD IN THE MUNI CODE
 IS 2 4 INCH STRIPES WITH 12 INCHES BETWEEN THE STRIPES.
 PLEASE NOTE THE STATE ALLOWS THE JURISDICTION TO DECIDE
 SINGLE STRIPE OR DOUBLE STRIPE AND THE DIMENSIONS
 BETWEEN THE STRIPES. 2017 FBC-ACCESSIBILITY CODE
 ADVISORY 502.3.3 MARKINGS. THE METHOD AND COLOR OF
 MARKINGS ARE NOT SPECIFIED BY THIS REQUIREMENT BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS AND REGULATIONS.
 THE CITY OF WES PALM BEACH MUNI CODE ARTICLE XV 94-485
 PARKING PROVIDE A DOUBLE LINED DIMENSIONED PARKING
 STALL DETAIL.
  
 7-10) COMPLIED.
  
  
 11) PROVISO/ DEFERRED SUBMITTALS PRODUCT APPROVALS FOR
 COMPONENTS & CLADDING.
  
 12) PROVISO / PORT COCHERE UNDER SEPARATE PERMIT,
 REVIEW AND ASSOCIATED FEES.
  
 13-16) COMPLIED.2ND REVIEW. THE RESPONSE INDICATES LIST
 OF DEFERRED SUBMITTALS IS FOUND ON SHEET A601. THIS
 SHEET HAS NEVER BEEN REVISED. W.P. B. AMENDMENT
 107.3.4.2 DEFERRED SUBMITTALS. COMPONENTS AND CLADDING
 WERE SUBMITTED AS EXHIBITS A-E. PLEASE NOTE SINCE THE
 SUBMITTED PRODUCT APPROVALS ARE GOING THROUGH REVIEW
 ANY PRODUCT APPROVAL BEING SUBMITTED EACH PRODUCT
 APPROVAL WOULD THEN BE CONSIDERED SINCE THE CITY HAS
 PUT IN PLAN REVIEW TIME ON THE DOCUMENTS SUBMITTED AT
 TIME OF APPLICATION.
  
 17) PROVISO; NOT APPLICABLE EXTERIOR WORK ONLY WILL
 RELATE TO PERMIT # 19120241 INT. REMODELING OF THE
 CORRIDORS AND PUBLIC SPACES.
  
 18) PROVISO: NOT APPLICABLE EXTERIOR WORK ONLY WILL
 RELATE TO PERMIT # 19120241 INT. REMODELING OF THE
 CORRIDORS AND PUBLIC SPACES.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  