| Date |
Text |
| 2020-05-14 08:41:50 | 2ND REVIEW FBC-2017 FUEL GAS |
| | PERMIT 19110539 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENT #1 FROM THE 1ST REVIEW LISTED BELOW WAS NOT |
| | ADDRESSED ON THE RESUBMITTED PLANS, AND THERE WAS NO |
| | NARRATIVE RESPONSE PROVIDED. PLEASE COMPLY WITH THE |
| | COMMENTS. |
| | |
| | GAS COMMENTS: |
| | 1. 2017 FLORIDA FUEL GAS CODE AND 2017 FBC 2017-107.2.1 |
| | AND NFPA 1. ALL THAT IS SHOWN ON THESE DRAWINGS IS A |
| | CONNECTION OF A NEW GAS LINE TO AN EXISTING GAS LINE |
| | FOR AN OUTDOOR FIRE PIT. THERE HAS BEEN NO SUBMITTAL OF |
| | THE FIRE PIT AS PART OF THE DOCUMENTS. THERE IS NO GAS |
| | RISER DIAGRAM SHOWING THE LONGEST LENGTH METHOD OF PIPE |
| | SIZING, ANY EXISTING APPLIANCES AND THE BTUH VALUES, |
| | VALVING, DIRT LEGS, ETC. PLEASE ALSO TO THE CITY OF |
| | WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS FOR |
| | OTHER INFORMATION THAT MAY BE REQUIRED ON THE |
| | DOCUMENTS. |
| | |
| | 2) NEW COMMENT- GAS ISOMETRIC DRAWING REQUIREMENTS: |
| | |
| | A) PLEASE NOTE WHEN PREPARING THE ISOMETRIC DRAWING |
| | THAT THE TOTAL LOAD OF THE NEW FIRE PIT SYSTEM MUST BE |
| | ADDED TO THE TOTAL LOAD OF THE EXISITNG SYSTEM TO |
| | ENSURE THE EXISTING SYSTEM AND MAIN GAS LINE ARE |
| | PROPERLY SIZED- SECTION 107.2.1 WPB |
| | |
| | B) SHOW THE PIPING RUN FROM THE METER TO THE MOST |
| | REMOTE OUTLET, INDICATE THE TOTAL LENGTH OF THE RUN, |
| | AND THE LENGTHS OF EACH BRANCH LINE SUPPLY A GAS |
| | APPLIANCE- SECTIONS 402.4.1, 402.4.2 FBC FG .INDICATE |
| | THE TYPES AND SIZES OF ALL PIPING IN THE SYSTEM. |
| | |
| | C) SHOW THE TOTAL BTUH LOAD OF THE SYSTEM AND THE BTUH |
| | LOAD OF EACH INDIVIDUAL APPLIANCE- SECTIONS 401.8 AND |
| | 402.2 FBC FG. |
| | |
| | D) INDICATE THE DELIVERY PRESSURE AT THE METER, AND THE |
| | REDUCED PRESSURES AT ALL MP REGULATORS OR IN-LINE |
| | APPLIANCE REGULATORS- SECTIONS 402.1, 402.4.3 THRU |
| | 402.6 FBC FG. |
| | |
| | E) INDICATE THE PIPE SIZING TABLES USED- TABLES |
| | 402.4(1) THRU 402.4(37) FBC FG. |
| | |
| | F) REFER TO SECTIONS 601.1 AND 636.1 FBC FG, AND SUBMIT |
| | MANUFACTURER'S SPECIFICTIONS FOR THE FIRE PIT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | . |
| | |
| | |
| | |