2020-05-14 08:41:502ND REVIEW FBC-2017 FUEL GAS
 PERMIT 19110539
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #1 FROM THE 1ST REVIEW LISTED BELOW WAS NOT
 ADDRESSED ON THE RESUBMITTED PLANS, AND THERE WAS NO
 NARRATIVE RESPONSE PROVIDED. PLEASE COMPLY WITH THE
 COMMENTS.
  
 GAS COMMENTS:
 1. 2017 FLORIDA FUEL GAS CODE AND 2017 FBC 2017-107.2.1
 AND NFPA 1. ALL THAT IS SHOWN ON THESE DRAWINGS IS A
 CONNECTION OF A NEW GAS LINE TO AN EXISTING GAS LINE
 FOR AN OUTDOOR FIRE PIT. THERE HAS BEEN NO SUBMITTAL OF
 THE FIRE PIT AS PART OF THE DOCUMENTS. THERE IS NO GAS
 RISER DIAGRAM SHOWING THE LONGEST LENGTH METHOD OF PIPE
 SIZING, ANY EXISTING APPLIANCES AND THE BTUH VALUES,
 VALVING, DIRT LEGS, ETC. PLEASE ALSO TO THE CITY OF
 WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS FOR
 OTHER INFORMATION THAT MAY BE REQUIRED ON THE
 DOCUMENTS.
  
 2) NEW COMMENT- GAS ISOMETRIC DRAWING REQUIREMENTS:
  
 A) PLEASE NOTE WHEN PREPARING THE ISOMETRIC DRAWING
 THAT THE TOTAL LOAD OF THE NEW FIRE PIT SYSTEM MUST BE
 ADDED TO THE TOTAL LOAD OF THE EXISITNG SYSTEM TO
 ENSURE THE EXISTING SYSTEM AND MAIN GAS LINE ARE
 PROPERLY SIZED- SECTION 107.2.1 WPB
  
 B) SHOW THE PIPING RUN FROM THE METER TO THE MOST
 REMOTE OUTLET, INDICATE THE TOTAL LENGTH OF THE RUN,
 AND THE LENGTHS OF EACH BRANCH LINE SUPPLY A GAS
 APPLIANCE- SECTIONS 402.4.1, 402.4.2 FBC FG .INDICATE
 THE TYPES AND SIZES OF ALL PIPING IN THE SYSTEM.
  
 C) SHOW THE TOTAL BTUH LOAD OF THE SYSTEM AND THE BTUH
 LOAD OF EACH INDIVIDUAL APPLIANCE- SECTIONS 401.8 AND
 402.2 FBC FG.
  
 D) INDICATE THE DELIVERY PRESSURE AT THE METER, AND THE
 REDUCED PRESSURES AT ALL MP REGULATORS OR IN-LINE
 APPLIANCE REGULATORS- SECTIONS 402.1, 402.4.3 THRU
 402.6 FBC FG.
  
 E) INDICATE THE PIPE SIZING TABLES USED- TABLES
 402.4(1) THRU 402.4(37) FBC FG.
  
 F) REFER TO SECTIONS 601.1 AND 636.1 FBC FG, AND SUBMIT
 MANUFACTURER'S SPECIFICTIONS FOR THE FIRE PIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
 .
  
  
  