Plan Review Notes
Plan Review Notes For Permit 19110539
Permit Number 19110539
Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-13 11:42:031ST REVIEW: 19110539
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. ON ROOFS WHERE PONDING COULD OCCUR IF THE PRIMARY
 DRAIN IS CLOGGED A EMERGENCY OVERFLOW ROOF DRAIN IS
 REQUIRED. PER FBC PL 1108.1
  
 2. PROVIDE SIZING CALCULATION FOR ALL NEW ROOF DRAINS .
 PER FBC PL 1106.2
  
 3.SHT. P200 GENERAL NOTE 1(E) PLUMBING CONTRACTOR SHALL
 BE LICENSED BY STATE OF FLORIDA. PER FAC 589
  
 4. SHT. P200 GENERAL NOTE # 14 (A) STORM PIPING NOT
 PERMITTED TO DISCHARGE TO SANITARY SEWER. PER WPB
 ORDINANCE
  
 5. SHT. P200 SHOW STORM PIPING FOR STAIR WELLS. PER WPB
 AMEND TO FBC 107.2.1
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]