Plan Review Notes
Plan Review Notes For Permit 19110539
Permit Number 19110539
Review Stop G
Sequence Number 1
Notes
Date Text
2020-03-27 13:56:02FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC P = FBC PLUMBING
  
 FAILED
  
 PLEASE NOTE THAT THE RESPONSES TO THE PREVIOUS PLUMBING
 COMMENTS ARE ACCEPTABLE, HOWEVER WE HAVE TO ADD
 COMMENTS FOR THE GAS OUTDOOR FIRE PIT.
  
 GAS COMMENTS:
 1. 2017 FLORIDA FUEL GAS CODE AND 2017 FBC
 2017-107.2.1 AND NFPA 1. ALL THAT IS SHOWN ON THESE
 DRAWINGS IS A CONNECTION OF A NEW GAS LINE TO AN
 EXISTING GAS LINE FOR AN OUTDOOR FIRE PIT. THERE HAS
 BEEN NO SUBMITTAL OF THE FIRE PIT AS PART OF THE
 DOCUMENTS. THERE IS NO GAS RISER DIAGRAM SHOWING THE
 LONGEST LENGTH METHOD OF PIPE SIZING, ANY EXISTING
 APPLIANCES AND THE BTUH VALUES, VALVING, DIRT LEGS,
 ETC. PLEASE ALSO TO THE CITY OF WEST PALM BEACH GAS
 PERMIT APPLICATION REQUIREMENTS FOR OTHER INFORMATION
 THAT MAY BE REQUIRED ON THE DOCUMENTS.
  
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  