2020-01-06 14:38:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET G 000 - UNDER THE CODE INFORMATION: FIRE
 PREVENTION, THERE IS AN INDICATION OF FLORIDA BUILDING
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 FLORIDA FIRE PREVENTION CODE; 6TH EDITION.
  
 PLEASE ENSURE COMPLIANCE AND CORRECT.
  
  
  
 2) SHEET G 101 - THERE IS AN INDICATION OF A FIRE PIT -
 HOW WILL PROTECTION BE PROVIDED TO PREVENT THE
 POSSIBLITIY OF ACCIDENTAL TOUCHING AND CONTACT WITH THE
 FLAME?
  
 PER NFPA 1
 10.10.8 INCINERATORS AND FIREPLACES.
 10.10.8.1 INCINERATORS, OUTDOOR FIREPLACES, PERMANENT
 BARBECUES,
 AND GRILLS SHALL NOT BE BUILT, INSTALLED, OR MAINTAINED
 WITHOUT PRIOR
 APPROVAL OF THE AHJ.
 10.10.8.2 INCINERATORS, OUTDOOR FIREPLACES, PERMANENT
 BARBECUES,
 AND GRILLS SHALL BE MAINTAINED IN GOOD REPAIR AND IN A
 SAFE
 CONDITION AT ALL TIMES.
 10.10.8.3 OPENINGS IN INCINERATORS, OUTDOOR FIREPLACES,
 PERMANENT
 BARBECUES, AND GRILLS SHALL BE PROVIDED WITH AN
 APPROVED SPARK
 ARRESTER, SCREEN, OR DOOR.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) SHEET G 101 - THERE IS AN INDICATION OF A FIRE PIT
 EMERGENCY SHUTOFF. - THE EMERGENCY SHUT OFF SHALL BE
 REMOTE FORM THE FIRE PIT ITSELF.
  
 PLEASE PROVIDE AN ALTERNATE SHUTOFF THAT IS NOT LOCATED
 AT THE ACTUAL FIRE PIT LOCATION.
  
  
  
 4) NO LIFE SAFETY SHEET - THERE ARE INDICATIONS OF WORK
 IN AND AROUND THE REQUIRED MEAND OF EGRESS AND EXITING.
  
 HOW WILL THE REQUIRED EXIT EGRESS AND EXIT DISCHARGES
 BE MAINTAINED THROUGHOUT CONSTRUCTION.
  
 PER NFPA 101 CH. 7, MEANS OF EGRESS
  
 7.5 ARRANGEMENT OF MEANS OF EGRESS.
 7.5.1 GENERAL.
 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL
 BE ARRANGED, SO
 THAT EXITS ARE READILY ACCESSIBLE AT ALL TIMES.
 7.5.1.1.1* WHERE EXITS ARE NOT IMMEDIATELY ACCESSIBLE
 FROM AN
 OPEN FLOOR AREA, CONTINUOUS PASSAGEWAYS, AISLES, OR
 CORRIDORS
 LEADING DIRECTLY TO EVERY EXIT SHALL BE MAINTAINED AND
 SHALL BE
 ARRANGED TO PROVIDE ACCESS FOR EACH OCCUPANT TO NOT
 LESS THAN TWO
 EXITS BY SEPARATE WAYS OF TRAVEL, UNLESS OTHERWISE
 PROVIDED IN
 7.5.1.1.3 AND 7.5.1.1.4.
  
 7.5.2.2* EXIT ACCESS AND EXIT DOORS SHALL BE DESIGNED
 AND ARRANGED
 TO BE CLEARLY RECOGNIZABLE.
  
  
 PLEASE REVIEW AND PROVIDE A LIFE SAFETY PLAN.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  