Plan Review Notes
Plan Review Notes For Permit 19110539
Permit Number 19110539
Review Stop B
Sequence Number 1
Notes
Date Text
2020-01-27 14:14:27 
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110539
 ADD: 600 NORTHPOINT PARKWAY
 CONT: TBD/ TO BE DETERMINED
 TEL: ????????????????????
 E-MAIL: [email protected] CONTACT: ASHLEE
 CALLAHAN
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 27TH/ 2020
 ACTION: DENIED
  
 1) ON THE PERMIT APPLICATION THERE ARE 2 VALUES FOR THE
 PROJECT, $750,000 AND $75,000 DOLLARS OF VALUE. THE
 APPLICATION UNDER THE HEADING WORK DESCRIPTION STATES:
 FA?ADE RENOVATION/ IMPROVEMENTS WITH NEW CLADDING AND
 ARCHITECTURAL FEATURES IN LIMITED SELECT AREAS + PORTE
 COCHERE REPLACEMENT. PLEASE EXPLAIN WHY THE COST BREAK
 OUT?
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET G100 THE EXISTING SITE DIAGRAM STATES THE NEW
 PORTE COCHERE PROVIDED BY THE OWNER, INSTALLED BY
 OTHERS. IF THE PORTE COCHERE IS BEING PROVIDED BY THE
 OWNER, DOES THE COST OF THE PORTE COCHERE (MATERIALS,
 LABOR, ENGINEERING, OVERHEAD & PROFIT FOR THE
 CONTRACTOR FIGURED INTO ONE OF THE DOLLAR AMOUNTS
 LISTED ABOVE? IT WOULD APPEAR THAT A 2ND PERMIT WILL
 NEED TO BE APPLIED FOR AS WELL AS CONTRACTOR FOR THIS
 PORTION OF THE JOB?
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) THE SHEET G100 STATES THE NEW PORTE COCHERE PROVIDED
 BY THE OWNER, INSTALLED BY OTHERS. IS THE ARCHITECT OF
 RECORD TO BE OVER BOTH OF THE STRUCTURAL ENGINEERS? OR
 IS THE STRUCTURAL ENGINEER FOR THE BUILDING THE
 STRUCTURAL ENGINEER OF RECORD AND THE PORT COCHERE
 ENGINEER A DELEGATE ENGINEER TO THE STRUCTURAL
 ENGINEER? FLORIDA ADMINISTRATIVE CODE 61G15-31.001.
  
 4) THE ISSUE WITH 2 GENERAL CONTRACTORS ON THE SAME
 SITE AND ONE SET OF PLANS. PLEASE BREAK OUT THE PLAN
 INFORMATION FOR THE PORTE COCHERE INTO A SEPARATE
 PERMIT AND PLANS. THERE NEEDS TO BE A DEFINITE
 DISTINCTION AS WHAT WORK BELONGS TO WHICH CONTRACTOR.
 FOR EXAMPLE ELECTRICAL, ROOFING AND FIRE SPRINKLERS.
 107.2.1.2. ADDITIONAL INFORMATION REQUIRED.
  
 5) THE PORTE COCHERE TO BE CONSIDERED PART OF THE 3
 STORY BUILDING WOULD REQUIRE SPRINKLERS, FOR A BUILDING
 TYPE 5A, OTHERWISE YOU ARE LOOKING AT 2 SEPARATE
 BUILDINGS ON THE SAME LOT AND AN ASSUMED PROPERTY LINE.
 YOU NOW HAVE 2 SEPARATE BUILDINGS ON THE SAME LOT.
 503.1.2 BUILDINGS ON SAME LOT. TWO OR MORE BUILDINGS ON
 THE SAME LOT SHALL BE REGULATED AS SEPARATE BUILDINGS
 OR SHALL BE CONSIDERED AS PORTIONS OF ONE BUILDING
 WHERE THE BUILDING HEIGHT, NUMBER OF STORIES OF EACH
 BUILDING AND THE AGGREGATE BUILDING AREA OF THE
 BUILDINGS ARE WITHIN THE LIMITATIONS SPECIFIED IN
 SECTIONS 504 AND 506. THE PROVISIONS OF THIS CODE
 APPLICABLE TO THE AGGREGATE BUILDING SHALL BE
 APPLICABLE TO EACH BUILDING.
  
 6) SHEET G100 THE EXISTING SITE DIAGRAM INDICATES AN
 EXISTING PARKING OF 215 SPACES, OF THESE 7 PARKING
 SPACES ARE SET UP TO BE ACCESSIBLE PARKING SPACES. NOTE
 5 STATES THE ACCESSIBLE PARKING SPACES ARE TO BE
 RE-GRADED AND RE-STRIPED. THE NOTE STATES THE RE-STRIPE
 OF THE PARKING SPACES TO MINIMUM DIMENSIONS SHOWN PER
 THE 2012 FLORIDA ACCESSIBILITY CODE REQUIREMENTS.
 PLEASE REFER TO THE 2017 FBC-ACCESSIBILITY CODE AND
 WEST PALM BEACH CITY ACCESSIBLE PARKING STANDARD. AN
 ACCESSIBLE PARKING SPACE AND ACCESS AISLE, PLEASE SEE
 THE 2017 FBC-ACCESSIBILITY CODE 502.3.3 MARKING. ACCESS
 AISLES SHALL BE MARKED SO AS TO DISCOURAGE PARKING IN
 THEM. THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED. FLORIDA LAW,
 S.553.5041(5)(C)1., REQUIRES DIAGONAL STRIPING OF
 ACCESS AISLES. THE CITY OF W. P. B. MUNI CODE ARTICLE
 XV 94-485 PARKING PROVIDES A DOUBLE LINED DIMENSIONED
 PARKING STALL DETAIL.
  
 7) SHEET G100 THE EXISTING SITE DIAGRAM INDICATES WITH
 NOTE NUMBER 9 TO PROVIDE A NEW CURB WITH FLUSH
 TRANSITION AND 5 FOOT WIDE SIDEWALK TO THE NEW
 ACCESSIBLE PARKING SPACE. WITH THE REGRADING OF THE
 OTHER ACCESSIBLE PARKING SPACES WILL THERE POSSIBLY BE
 ADDITIONAL WORK TO MAKE THE TRANSITION FROM THE ACCESS
 AISLE TO THE SIDEWALK? ARE THE OTHER DROPPED AT THE
 ACCESS AISLE AND IN COMPLIANCE WITH 406 CURB RAMPS OF
 THE 2017 ACCESSIBILITY CODE, FBC.
  
 8) SHEET G100 THE EXISTING SITE DIAGRAM ALSO INDICATES
 THE RE-USE OF THE EXISTING GATES TO THE POOL. THERE ARE
 ABBREVIATIONS RFID LATCH ASSEMBLY, AND RFID EXIT
 DEVICE, THIS ABBREVIATION IS NOT LISTED ON THE
 COVERSHEET. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED. PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B
 SECTION 454.1.3.1.9. LATCHING REQUIREMENTS.
  
 9) SHEET S001 NOTE 2. WIND LOAD PER ASCE 7 IS LISTED AS
 A B EXPOSURE. IN THE ASCE 7-10 26.7.3 EXPOSURE
 CATEGORIES. THE EXPOSURE B PREVAILS IN THE UPWIND
 DIRECTION FOR A DISTANCE GREATER THAN 2,600 FT. OR 20
 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER.
 YOU CAN SHOOT A VECTOR TO THE SOUTHEAST OF THE SITE
 DOWN THE I-95 CORRIDOR FOR OVER 3,000 FT. BEFORE ANY
 OBJECTS OCCUR. FOR SITES LOCATED IN TRANSITION ZONES
 BETWEEN EXPOSURE CATEGORIES, THE CATEGORY RESULTING IN
 THE LARGEST WIND FORCE SHALL BE USED. ASCE 7-10 SECTION
 26.7.1 WIND DIRECTION AND SECTORS DOES NOT REQUIRE THE
 MORE STRINGENT WIND EXPOSURE FROM ALL SECTORS AS STATED
 ON THE PLAN SHEET.
  
 10) NEITHER THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL
 SHEETS PROVIDE THE PRESSURES FOR COMPONENTS AND
 CLADDING. WE WILL NEED PRESSURES IN VASD FOR FLAT ROOFS
 AS WELL AS FOR SLOPED ROOFS FOR ROOF ZONES 1,2 & 3 AS
 WELL AS WALL ZONES 4 & 5. ASCE 7-10 FIGURE 30.5-1.
  
 11) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, NICHIHA PANELS
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
  
 12A) SHEET S201 SHOWS NEW STEEL MEMBERS WITH BOLTED AND
 WELDED CONNECTIONS, PLEASE PROVIDE COMPLIANCE WITH:
 WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING. SPEAK WITH THE CHIEF
 BUILDING INSPECTOR ABOUT 3RD PARTY CERTIFICATION OF
 BOLTED ASSEMBLIES. IF THERE IS ANY QUESTIONS ABOUT THE
 CODE REQUIREMENTS FOR THIS SECTION, PLEASE CONTACT THE
 CHIEF BUILDING INSPECTOR KEN CONRAD AT 561-805-6666.
 THANK YOU.
  
 12B) THE COVERSHEET LIST THE BUILDING TYPE AS
 CONSTRUCTION TYPE 5A. WITH ALL OF THE STEEL COLUMNS,
 BEAMS THE PLANS DOES NOT INDICATE HOW COMPLIANCE WITH
 TABLE 601 OF THE 2017 FBC-BUILDING A 1 HOUR FIRE RATING
 WILL BE ACHIEVED. THE SAME 1 HOUR RATING WILL ALSO NEED
 TO BE PROVIDED ON THE STRUCTURAL MEMBERS OF THE
 PROPOSED PAVILION.
  
 13) PLEASE PROVIDE IN A WRITTEN STATEMENT IF THE
 PRODUCT APPROVALS ARE TO BE SUBMITTED AFTER PERMIT
 ISSUANCE. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 15) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2017 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 16) FOR THE NICHIHA PRODUCT APPROVAL REPORT IDENTIFY,
 CIRCLE THE MODEL, NUMBER OR NAME OF THE SYSTEM TO BE
 INSTALLED. UNDER THE INSTALLATION INSTRUCTIONS CIRCLE
 THE TYPE OF SIDING, FASTENER, SPACING, TYPE OF WALL
 FRAMING THE ALLOWABLE DESIGN PRESSURE VASD AND VULT
 PRESSURES FOR VULT. THANK YOU.
  
 17) THERE IS NO LIFE SAFETY PLAN OF THE RE-CONFIGURED
 LOBBY, MISSING THE OCCUPANT LOAD, THE FLOOR PLAN SHOWS
 ONLY ONE MEANS OF EGRESS, COMMON PATH OF TRAVEL IS NOT
 PROVIDED AND THE WIDTH OF THE ENTRY DOORS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 18) SHEET A-341 THE MAIN ENTRY SHOWS THE S-BAR AND
 COMMUNAL TABLE BUT NO DETAILS FOR ACCESSIBILITY. THE
 LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE;
 18A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 18B) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 18C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 18D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 18E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 18E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 19)A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  