Plan Review Notes
Plan Review Notes For Permit 19110517
Permit Number 19110517
Review Stop M
Sequence Number 3
Notes
Date Text
2020-03-02 08:39:083RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19110517
 3/2//20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 2ND REVIEW PRINTED BELOW HAVE NOT
 BEEN ADDRESSED- PLEASE COMPLY.
  
 1) M-1: MECHANICAL VENTILATION IS REQUIRED FOR THE
 ENLARGED BATHROOM IN ACCORDANCE WITH SECTION 1203.5.2.1
 FBC B. PLEASE PROVIDE A MINIMUM 50 CFM EXHAUST FAN- SEE
 TABLE 403.3.1.1 FBC M.
  
 2) M-1: VERIFY THAT ALL OCCUPIED ROOMS AND SPACES ARE
 PROVIDED WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS
 CAPABLE OF MAINTAINING AN INDOOR TEMPERATURE OF NOT
 LESS THAN 68 DEGREES F- SECTION 309.1 FBC M.
  
 3) M-1: PLEASE RESUBMIT TWO SETS OF CORRECTED PLANS-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  