| Date |
Text |
| 2020-03-02 08:39:08 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19110517 |
| | 3/2//20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENTS FROM THE 2ND REVIEW PRINTED BELOW HAVE NOT |
| | BEEN ADDRESSED- PLEASE COMPLY. |
| | |
| | 1) M-1: MECHANICAL VENTILATION IS REQUIRED FOR THE |
| | ENLARGED BATHROOM IN ACCORDANCE WITH SECTION 1203.5.2.1 |
| | FBC B. PLEASE PROVIDE A MINIMUM 50 CFM EXHAUST FAN- SEE |
| | TABLE 403.3.1.1 FBC M. |
| | |
| | 2) M-1: VERIFY THAT ALL OCCUPIED ROOMS AND SPACES ARE |
| | PROVIDED WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS |
| | CAPABLE OF MAINTAINING AN INDOOR TEMPERATURE OF NOT |
| | LESS THAN 68 DEGREES F- SECTION 309.1 FBC M. |
| | |
| | 3) M-1: PLEASE RESUBMIT TWO SETS OF CORRECTED PLANS- |
| | SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE |
| | RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. |
| | THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |