2020-01-30 15:29:27FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 CCFH= CHILD CARE FACILITY HANDBOOK
  
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
 FBC EX 1006.1
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
 1. BATHROOM SHALL COMPLY WITH ACCESSIBILITY
 REQUIREMENTS IN ACCORDANCE WITH FBC ACC. PER WPB FBC
 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC CHAPTERS 3 AND
 6 PROVIDE DETAILS INDICATING THE FOLLOWING:
 A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 H. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
 I. BATHTUB SHALL BE PROVIDED GRAB BARS, REMOVABLE SEAT
 AND CONTROLS/SHOWER SPRAY UNIT IN ACCORDANCE WITH FBC
 ACC 607.4.2, 607.4.2.1, 607.4.2.2, 607.4.2.3, 607.5 AND
 607.6MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 J. SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1 OR
 304.3.2.
 K. DOORS SHALL NOT BE PERMITTED TO SWING INTO TURNING
 SPACES PER FBC ACC 304.4.
 L. SHOW CLEAR FLOOR SPACES FOR TUB AND LAVATORY. THE
 CLEAR FLOOR OR GROUND SPACE SHALL BE 30 INCHES (760 MM)
 MINIMUM BY 48 INCHES (1220 MM) MINIMUM AND COMPLY WITH
 FBC ACC SECTION 305.
  
 FBC EX 1010.1
 WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF
 AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED OR DIFFERENT PLUMBING
 FIXTURE REQUIREMENTS OR TO INCREASED WATER SUPPLY
 REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, PLUMBING, THE NEW OCCUPANCY SHALL COMPLY WITH THE
 INTENT OF THE RESPECTIVE FLORIDA BUILDING CODE,
 PLUMBING PROVISIONS.
 1. PER WPB FBC 107.2.1, PROVIDE A SANITARY RISER
 DIAGRAM AND PLAN VIEW SHOWING THE REVISED SANITARY
 PIPING AND FIXTURE LAYOUT TO ACCOMMODATE THE LAYOUT OF
 THE ACCESSIBLE BATHROOM. COMPLY WITH FBC PL CHAPTER 7
 AND CHAPTER 9.
 2. PER FBC PL 416.5, PROVIDE TEMPERED WATER FROM THE
 LAVATORY. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 3. PER FBC PL 424.3, PROVIDE INDIVIDUAL SHOWER OR
 TUB-SHOWER COMBINATION VALVES THAT IS
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES AND CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER
 COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION.
 4. PER WPB FBC 107.1.2, PROVIDE FOR REVIEW, PROVIDE
 DATA FOR EGRESS, TO INCLUDE BREAKDOWN FOR STORAGE AND
 DAY CARE AREA AS WELL AS OCCUPANCY E TO ESTABLISH
 MAXIMUM OCCUPANT LOAD FOR THE STRUCTURE WHICH SHALL BE
 APPLICABLE TO MINIMUM PLUMBING REQUIREMENTS.IT WILL BE
 IMPORTANT TO SHOW, IF THERE IS ANOTHER BATHROOM ON THE
 SECOND FLOOR, AS THIS MAY BE HELPFUL IN MEETING MINIMUM
 FIXTURE REQUIREMENTS IF NEED BE BASED ON FINAL
 OCCUPANCY DETERMINATION.
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
 INFORMATIONAL COMMENTS
 1. PLEASE REFER TO FAC 65C-22.001, REGARDING THE ?CHILD
 CARE FACILITY HANDBOOK? BELOW. THERE IS A KITCHEN IN
 THE STRUCTURE. IF THE FACILITY IS PREPPING/HANDLING
 FOOD FOR THE CLIENTS, THEN PER CCFH SECTION 3.9 (7) A
 SEPARATE HAND WASHING SINK IS REQUIRED. IF THIS IS THE
 CASE, THEN THE SANITARY RISER DIAGRAM AND PLAN VIEW
 SHALL INCLUDE THE HAND SINK.
 2. PLEASE REFER TO FAC 65C-22.001, REGARDING THE ?CHILD
 CARE FACILITY HANDBOOK? BELOW. PER CCFH SECTION 3.7 (1)
 PROVIDE EASY ACCESS FOR CHILDREN USING THE TOILET
 FACILITIES; THIS MAY BE ACCOMPLISHED BY PROVIDING
 STRUCTURES THAT ARE SAFELY CONSTRUCTED AND HAVE AN
 IMPERVIOUS SURFACE THAT CAN BE EASILY CLEANED AND
 SANITIZED. STRUCTURES SHOULD BE IN PLACE FOR STATE
 INSPECTION.
 3. PLEASE REFER TO FAC 65C-22.001, REGARDING THE ?CHILD
 CARE FACILITY HANDBOOK? BELOW. PER CCFH SECTION 3.9.8
 PROVIDE CLEAN, SANITARY DRINKING WATER READILY
 ACCESSIBLE AREAS, THROUGHOUT THE DAY. SINK/WATER
 FOUNTAIN COMBINATIONS ARE PROHIBITED FOR
 HANDWASHING SINKS THAT ARE USED FOR HYGIENE PROCEDURES
 AFTER TOILETING OR DIAPER
 CHANGING.
  
 FS 402.305 LICENSING STANDARDS; CHILD CARE FACILITIES.
 (5) PHYSICAL FACILITIES.--MINIMUM STANDARDS SHALL
 INCLUDE REQUIREMENTS FOR BUILDING CONDITIONS, INDOOR
 PLAY SPACE, OUTDOOR PLAY SPACE, NAPPING SPACE,
 "BATHROOM FACILITIES", "FOOD PREPARATION FACILITIES",
 OUTDOOR EQUIPMENT, AND INDOOR EQUIPMENT. BECAUSE OF THE
 NATURE AND DURATION OF DROP-IN CHILD CARE, OUTDOOR PLAY
 SPACE AND OUTDOOR EQUIPMENT SHALL NOT BE REQUIRED FOR
 LICENSURE; HOWEVER, IF SUCH PLAY SPACE AND EQUIPMENT
 ARE PROVIDED, THEN THE MINIMUM STANDARDS SHALL APPLY TO
 DROP-IN CHILD CARE. WITH RESPECT TO MINIMUM STANDARDS
 FOR PHYSICAL FACILITIES OF A CHILD CARE PROGRAM FOR
 SCHOOL-AGE CHILDREN WHICH IS OPERATED IN A PUBLIC
 SCHOOL FACILITY, THE DEPARTMENT SHALL ADOPT THE STATE
 UNIFORM BUILDING CODE FOR PUBLIC EDUCATIONAL FACILITIES
 CONSTRUCTION AS THE MINIMUM STANDARDS, REGARDLESS OF
 THE OPERATOR OF THE PROGRAM. THE LEGISLATURE INTENDS
 THAT IF A CHILD CARE PROGRAM FOR SCHOOL-AGE CHILDREN IS
 OPERATED IN A PUBLIC SCHOOL, THE PROGRAM NEED NOT
 CONFORM TO STANDARDS FOR PHYSICAL FACILITIES OTHER THAN
 THE STANDARDS ADOPTED BY THE COMMISSIONER OF EDUCATION.
 FAC 65C-22.001
 (6) CHILD CARE STANDARDS. CHILD CARE PROGRAMS MUST
 FOLLOW THE STANDARDS FOUND IN THE ?CHILD CARE FACILITY
 HANDBOOK,? MAY 2019, INCORPORATED HEREIN BY REFERENCE.
 PLEASE SEE EXCERPTS FROM THE ?CHILD CARE FACILITY
 HANDBOOK? ATTACHED TO RETURNED PLAN. THE HANDBOOK MAY
 BE OBTAINED FROM THE DEPARTMENT?S WEBSITE AT
 WWW.MYFLFAMILIES.COM/CHILDCARE OR FROM THE FOLLOWING
 LINK: HTTP://WWW.FLRULES.ORG/GATEWAY/REFERENCE.ASP?NO=R
 EF-11491
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19110517 2017 WILKINS AVE