| 2020-01-23 14:17:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE IS ONLY ONE SET OF RESUBMITTED PLANS, TWO SETS |
| | ARE REQUIRED. |
| | |
| | PLEASE SUBMIT A COMPLETE 2ND SET. |
| | |
| | |
| | |
| | 2) THE DETAIL OF THE EXISITNG FA SYSTEM DOES NOT APPEAR |
| | TO MEET THE REQUIREMENT OF NFPA 101, CH 9 |
| | |
| | I AM NOT CERTAIN THAT THE INSTALLED SYSTEM BY XFINITY |
| | MEETS THE REQUIRMENT OF NFPA 101, CH 9 AND NFPA 72 |
| | |
| | 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL |
| | BE INSTALLED, |
| | TESTED, AND MAINTAINED IN ACCORDANCE WITH THE |
| | APPLICABLE |
| | REQUIREMENTS OF NFPA 70, NATIONAL ELECTRICAL CODE, AND |
| | NFPA |
| | 72, NATIONAL FIRE ALARM AND SIGNALING CODE, UNLESS IT |
| | IS AN |
| | APPROVED EXISTING INSTALLATION, WHICH SHALL BE |
| | PERMITTED TO BE |
| | CONTINUED IN USE. |
| | |
| | |
| | 9.6.2 SIGNAL INITIATION. |
| | 9.6.2.1 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE, |
| | ACTUATION |
| | OF THE FIRE ALARM SYSTEM SHALL OCCUR BY ANY OR ALL OF |
| | THE FOLLOWING |
| | MEANS OF INITIATION BUT SHALL NOT BE LIMITED TO SUCH |
| | MEANS: |
| | (1) MANUAL FIRE ALARM INITIATION |
| | (2) AUTOMATIC DETECTION |
| | (3) EXTINGUISHING SYSTEM OPERATION |
| | 9.6.2.2 MANUAL FIRE ALARM BOXES SHALL BE USED ONLY FOR |
| | FIREPROTECTIVE |
| | SIGNALING PURPOSES. COMBINATION FIRE ALARM AND GUARD?S |
| | TOUR STATIONS SHALL BE PERMITTED. |
| | 9.6.2.3 A MANUAL FIRE ALARM BOX SHALL BE PROVIDED AS |
| | FOLLOWS, |
| | UNLESS MODIFIED BY ANOTHER SECTION OF THIS CODE: |
| | (1) FOR NEW ALARM SYSTEM INSTALLATIONS, THE MANUAL FIRE |
| | ALARM |
| | BOX SHALL BE LOCATED WITHIN 60 IN. (1525 MM) OF EXIT |
| | DOORWAYS. |
| | (2) FOR EXISTING ALARM SYSTEM INSTALLATIONS, THE MANUAL |
| | FIRE ALARM |
| | BOX EITHER SHALL BE PROVIDED IN THE NATURAL EXIT ACCESS |
| | PATH |
| | NEAR EACH REQUIRED EXIT OR WITHIN 60 IN. (1525 MM) OF |
| | EXIT |
| | DOORWAYS. |
| | |
| | 9.6.3.5 UNLESS OTHERWISE PROVIDED IN 9.6.3.5.1 THROUGH |
| | 9.6.3.5.8, |
| | NOTIFICATION SIGNALS FOR OCCUPANTS TO EVACUATE SHALL BE |
| | AUDIBLE, AND |
| | VISIBLE SIGNALS IN ACCORDANCE WITH NFPA 72, NATIONAL |
| | FIRE ALARM |
| | AND SIGNALING CODE. |
| | |
| | 9.6.3.7 AUDIBLE ALARM NOTIFICATION APPLIANCES SHALL BE |
| | OF SUCH |
| | CHARACTER AND SO DISTRIBUTED AS TO BE EFFECTIVELY HEARD |
| | ABOVE THE |
| | AVERAGE AMBIENT SOUND LEVEL THAT EXISTS UNDER NORMAL |
| | CONDITIONS |
| | OF OCCUPANCY. |
| | |
| | 16.3.4.5 DETECTION. A SMOKE DETECTION SYSTEM IN |
| | ACCORDANCE |
| | WITH SECTION 9.6 SHALL BE INSTALLED IN DAY-CARE |
| | OCCUPANCIES, OTHER |
| | THAN THOSE HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR |
| | OPENING |
| | DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN |
| | EXTERIOR EXIT ACCESS |
| | BALCONY IN ACCORDANCE WITH 7.5.3, AND SUCH SYSTEM SHALL |
| | COMPLY |
| | WITH BOTH OF THE FOLLOWING: |
| | (1) DETECTORS SHALL BE INSTALLED ON EACH STORY IN FRONT |
| | OF THE DOORS |
| | TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL FLOORS |
| | OCCUPIED BY |
| | THE DAY-CARE OCCUPANCY. |
| | (2) DETECTORS SHALL BE INSTALLED IN LOUNGES, RECREATION |
| | AREAS, AND |
| | SLEEPING ROOMS IN THE DAY-CARE OCCUPANCY. |
| | |
| | PLEASE PROVIDE DETAILS AND THE PERMIT NUMBER FOR |
| | CHANGES. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |