| Date |
Text |
| 2019-12-05 15:44:08 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19110517 |
| | 12/5/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE CHANGE OF OCCUPANCY FROM R-3 TO E-DAY CARE MAY |
| | RESULT IN AN INCREASE IN REQUIRED VENTILATION FOR ALL |
| | OCCUPIED ROOMS AND SPACES OF THE OCCUPANCY. PLEASE |
| | REFER TO SECTION 1009.1 FBC EX AND PROVIDE MINIMUM |
| | VENITLATION CALCULATIONS USING EITHER THE NATURAL |
| | VENTILATION METHOD PER SECTION 402 FBC M, OR THE |
| | MECHANICAL VENTILATION METHOD PER SECTION 403 FBC M. |
| | |
| | PLEASE SHOW THE CALCULATIONS ON THE PLAN. IF USING THE |
| | MECHANICAL METHOD PER TABLE 403.3.1.1, PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS |
| | OF OUTDOOR AIR. |
| | |
| | 2) SUBMIT MECHANICAL PLANS SHOWING ALL PLANNED OR |
| | REQUIRED ALTERATIONS TO THE EXISTING HVAC AND |
| | MECHANICAL SYSTEMS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |
| 2019-11-20 08:47:57 | REVIEWER, PLEASE SEE THE EMAIL CORRESPONDENCE FROM MR. |
| | BROWN. SEE ME IF YOU HAVE QUESTIONS. SAK |