Plan Review Notes
Plan Review Notes For Permit 19110517
Permit Number 19110517
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-11-20 12:28:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATIONS OF A FIRE ALARM AND THAT IT
 IS MONITORED BY CENTRAL MONITORING STATION.
  
 PER NFPA 101, CH 16, NEW DAY CARE OCCUPANCY
  
 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN
 DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR
 OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN
 EXTERIOR
 EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE
 PROVIDED
 WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION
 9.6.
  
 THERE ARE MULTIPLE ROOMS INDICATED, A FIRE ALARM IS
 REQUIRED.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGE TO
 INSTALL UNDER A SEPARATE PERMIT.
  
  
  
 2) THERE ARE NO INDICATIONS OF THE DOOR HARDWARE
  
 PER NFPA 101
  
 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS,
 STORAGE
 AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR AREAS
 SHALL BE SUCH
 THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE SPACE OR
 AREA.
 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE
 DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE
 OUTSIDE
 BY AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE
 TO THE STAFF.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF COMPLIANCE
  
  
  
 3) THERE APPEARS TO BE STAIRS LEADING TO A 2ND FL THAT
 IS ATTACHED TO OR WITHIN ONE OF THE DAY CARE ROOMS.
  
 WILL THIS 2ND FLOOR AREA BE USED?
  
 IF NOT, HOW WILL IT BE SEPARATED/CONTROLED FROM USE?
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AND
 NARRATIVE.
  
  
  
 4) THERE IS AN EXIT DOOR LEADING TO A PORCH INDICATED.
  
 THERE IS NO INDICATION OF HOW TO EXIT THE PORCH AREA.
  
 PLEASE PROVIDE DETAILS FOR WHEN YOU EXIT ONTO THE
 PORCH, HOW WILL YOU THEN EXIT THE PORCH?
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]