Plan Review Notes
Plan Review Notes For Permit 19110517
Permit Number 19110517
Review Stop B
Sequence Number 1
Notes
Date Text
2019-12-02 09:04:03BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19110577
 REVIEWED: DECEMBER 2, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 1004.1 DESIGN OCCUPANT LOAD. IN DETERMINING MEANS OF
 EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS FOR WHOM
 MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL BE
 DETERMINED IN ACCORDANCE WITH THIS SECTION
 -PLEASE PROVIDE DATA FOR EGREES, SQ. FOOTAGE BREAKDOWN
 OF SPACES AREAS MAY INCLUDE STORAGE AND DAY CARE AREA.
 SHOW SQ. FOOTAGE PER OCCUPANT EACH OCCUPANCY. THIS WILL
 ESTABLISH MAXIMUM OCCUPANT LOAD.
  
 2) 466.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE
 SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE
 CLOSET.
 -SHOW ON PLAN WHICH DOORS THIS APPLIES.
  
 3) 466.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL
 BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM
 THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE SHALL
 BE READILY ACCESSIBLE TO THE STAFF.
 -SHOW ON PLAN WHICH DOORS THIS APPLIES.
  
 4) 466.6.2 THE FOLLOWING ROOMS OR SPACES SHALL BE
 SEPARATED FROM THE REMAINDER OF THE BUILDING BY FIRE
 BARRIERS HAVING A FIRE-RESISTANCE RATING OF NOT LESS
 THAN 1 HOUR AND SHALL BE PROTECTED BY AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM. LAUNDRIES
 -SHOW ON PLAN WHICH WALLS WOULD BE 1 HOUR RATED AND HOW
 THIS IS ACHIEVED.
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  
2019-11-18 14:46:38REVIEWER, PLEASE SEE THE EMAIL CORRESPONDENCE FROM MR.
 BROWN. ADDITIONALLY, PLEASE ASSURE YOU NOTE IN THE
 REVIEW THAT THE OWNER LISTED IN BOX 3 ON THE APPLIATION
 FORM SHOULD BE CHANGED BY THE APPLICANT TO IDENTIFY THE
 THE LEASE HOLDER APPLICANT AND NOT THE FEE SIMPLE TITLE
 HOLDER. THE FEE SIMPLE TITILE HOLDER SHOULD BE LISTEED
 IN BOX 9 ON PAGE TWO OF THE APPLICATION. THE CHILD CARE
 APPLICATION TRAVELING WITH THIS SUBMITAL SHOULD BE
 FORWARDED TO MR. BROWN AT TIME OF ISSUANCE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved