| Plan Review Notes For Permit 19110505 |
| Permit Number |
19110505 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-12-05 16:54:43 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | FBC B 107, ENGINEERING PLANS, SPECIFICATIONS, REPORTS | | | OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED AND | | | SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION | | | 471.025, F.S., AND RULE 61G15-23.001, F.A.C. MUST BE | | | PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN | | | BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PERTIALLY | | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | |
|