| Date |
Text |
| 2019-11-12 12:44:25 | 1) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. |
| | SEC. G 2413.4.1, G2413.4.2. |
| | 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS |
| | APPLIANCES. 2017 FBC-FUEL GAS SEC. 304.1. WHERE |
| | COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL |
| | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS SEC.304.9.3 |
| | OR FBCR G2407.9.3. |
| | 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | 5) SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF |
| | VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE |
| | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER |
| | 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES. |
| | SEC.G2426 THROUGH G2439. |
| | 6) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE |
| | BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| | UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. NFPA |
| | 96-14. SECS. 10.4.1, 10.4.3, 10.4.4, 10.5.1. |
| | 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. |
| | |
| | NOTE - A COMPLETE AND THOROUGH REVIEW COULD NOT BE DONE |
| | AT THIS TIME DUE TO THE LACK OF REQUIRED INFORMATION ON |
| | THE PLANS / DRAWINGS AND ADDITIONAL PLAN REVIEW |
| | COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |