| 2019-11-19 07:27:16 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. VALUE FOR WORK STATED ON REVISION APPLICATION IS $0. |
| | THERE IS A SUBSTANTIAL AMOUNT OF INSTALLATION THAT HAS |
| | BEEN ADDED TO THE PLANS, AND THE INCREASED VALUE OF THE |
| | WORK MUST BE PROVIDED. PROVIDE COPY OF SIGNED CONTRACT |
| | WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL MATERIALS |
| | AND LABOR. THIS IS FOR TOTAL REVISION, NOT JUST |
| | ELECTRICAL. WPB FBC 109.3 |
| | 2. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| | EQUIPMENT PER CODE. NEC 210.63 |
| | 3. PANEL C LOAD CALCULATION IS DIFFERENT THAN THE |
| | ORIGINAL SET, BUT HAS NOT BEEN DOCUMENTED AS A CHANGE. |
| | HOWEVER, THE LOAD SHOWN IN THE PANEL SCHEDULE FOR THE |
| | ORIGINAL, AND IN THE REVISION, IS SHOWN AS 88.8 KVA. |
| | BUT THE LOAD CALCULATION BELOW THE PANEL SCHEDULE IN |
| | THE REVISION SUPPLIED SHOWS THE LOAD AS 64.8 KVA. |
| | PROVIDE CLARIFICATIONS AND/OR CORRECTIONS AS NEEDED. |
| | NEC 220; WPB FBC 107.2.1 |
| | 4. BASED ON COMMENT 3, IF THE LOAD IS ACTUALLY 88.8 |
| | KVA, THIS MEANS THE WIRE FEEDING THIS PANEL, AND THE |
| | BREAKER IN MDP FOR THIS PANEL, IS NOT SIZED PROPERLY. |
| | PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16); WPB FBC |
| | 107.2.1 |
| | 5. IN ADDITION TO COMMENT 4, THE EQUIPMENT GROUNDING |
| | CONDUCTOR(EGC) FOR THE FEED TO PANEL C IS NOT SIZED |
| | PROPERLY. PROVIDE CORRECTION. NEC 250.122 |
| | 6. THE EGC FEEDING PLC PANEL IS NOT SIZED PROPERLY. |
| | PROVIDE CORRECTION. NEC 250.122 |
| | 7. TOTAL LOAD SHOWN FOR PANEL D IS SHOWN AS 46.9 KVA. |
| | THIS EXCEEDS THE RATING OF THE TRANSFORMER SUPPLYING |
| | THIS LOAD. PROVIDE CORRECTION. NEC 110.3, 240.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |