2019-11-19 07:27:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON REVISION APPLICATION IS $0.
 THERE IS A SUBSTANTIAL AMOUNT OF INSTALLATION THAT HAS
 BEEN ADDED TO THE PLANS, AND THE INCREASED VALUE OF THE
 WORK MUST BE PROVIDED. PROVIDE COPY OF SIGNED CONTRACT
 WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL MATERIALS
 AND LABOR. THIS IS FOR TOTAL REVISION, NOT JUST
 ELECTRICAL. WPB FBC 109.3
 2. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 3. PANEL C LOAD CALCULATION IS DIFFERENT THAN THE
 ORIGINAL SET, BUT HAS NOT BEEN DOCUMENTED AS A CHANGE.
 HOWEVER, THE LOAD SHOWN IN THE PANEL SCHEDULE FOR THE
 ORIGINAL, AND IN THE REVISION, IS SHOWN AS 88.8 KVA.
 BUT THE LOAD CALCULATION BELOW THE PANEL SCHEDULE IN
 THE REVISION SUPPLIED SHOWS THE LOAD AS 64.8 KVA.
 PROVIDE CLARIFICATIONS AND/OR CORRECTIONS AS NEEDED.
 NEC 220; WPB FBC 107.2.1
 4. BASED ON COMMENT 3, IF THE LOAD IS ACTUALLY 88.8
 KVA, THIS MEANS THE WIRE FEEDING THIS PANEL, AND THE
 BREAKER IN MDP FOR THIS PANEL, IS NOT SIZED PROPERLY.
 PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16); WPB FBC
 107.2.1
 5. IN ADDITION TO COMMENT 4, THE EQUIPMENT GROUNDING
 CONDUCTOR(EGC) FOR THE FEED TO PANEL C IS NOT SIZED
 PROPERLY. PROVIDE CORRECTION. NEC 250.122
 6. THE EGC FEEDING PLC PANEL IS NOT SIZED PROPERLY.
 PROVIDE CORRECTION. NEC 250.122
 7. TOTAL LOAD SHOWN FOR PANEL D IS SHOWN AS 46.9 KVA.
 THIS EXCEEDS THE RATING OF THE TRANSFORMER SUPPLYING
 THIS LOAD. PROVIDE CORRECTION. NEC 110.3, 240.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  