2019-11-20 16:43:09***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 FBC B 107.2.1 MORE INFORMATION IS REQUIRED ON THE
 INSTALLATION SCHEDULE (WALL PRESSURES AND ANCHOR
 SPACING).
  
 FBC B 104.10/104.11 AND CITY OF WPB AMENDMENTS TO THE
 FBC B 104.10/104.11, PROVIDE AN ENGINEERS SIGNED AND
 SEALED DETAILED LETTER WITH CALCULATIONS TO CLARIFY THE
 REQUIRED ANCHORING OF PANELS TO MEET THE WINDLOADS FOR
 THE PROPOSED LOCATIONS OF OPENING PROTECTION.