| 2019-11-19 14:56:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PLEASE NOTE; A REVIEW OF MINIMUM PLUMBING FIXTURE |
| | REQUIREMENTS AS REQUIRED BY FBC ACC IS PART OF THE |
| | PLUMBING REVIEW PROCESS BUT IS TYPICALLY ADDRESSED ON |
| | THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING THESE |
| | REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED PRIOR TO |
| | A PLUMBING REVIEW APPROVAL. |
| | 1. RE: PLAN SHEET A-2.1.1; DETAIL A. PER WPB FBC |
| | 107.2.1, SHOW CLEAR FLOOR SPACE FOR BREAK ROOM SINK PER |
| | FBC ACC 305 AND 606.2. |
| | 2. RE: PLAN SHEET A-2.1.1; DETAIL 1. LAVATORIES AND |
| | SINKS SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER |
| | OF THE RIM OR COUNTER SURFACE 34 INCHES (865 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC |
| | 606.3. PER WPB FBC 107.2.1, CORRECT AS REQUIRED. |
| | 3. RE: PLAN SHEET A-2.1.1; DETAIL 8 AND 9. GRAB BARS |
| | SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES |
| | (840 MM) MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE PER FBC ACC 609.4. PER WPB FBC 107.2.1, CORRECT |
| | AS REQUIRED. |
| | 4. RE: PLAN SHEET A-2.1.1; DETAIL 8. PER FBC ACC 604.2, |
| | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION. PER WPB FBC 107.2.1, INDICATE THE SAME. |
| | 5. RE: PLAN SHEET A-2.1.1; DETAIL 8. PER FBC ACC 604.2, |
| | THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | (405 MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM FROM THE |
| | SIDE WALL OR PARTITION. PER WPB FBC 107.2.1, INDICATE |
| | THE SAME. |
| | 6. RE: PLAN SHEET A-2.1.1; DETAIL 8. PER FBC ACC 604.6, |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| | WATER CLOSET. PER WPB FBC 107.2.1, INDICATE THE SAME. |
| | 7. RE: PLAN SHEET A-2.1.1; DETAIL 9. PER FBC ACC 604.2, |
| | PER FBC ACC 604.7, TOILET PAPER DISPENSERS SHALL COMPLY |
| | WITH 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 |
| | INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET |
| | OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM |
| | AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR |
| | AND SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS |
| | SHALL NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT |
| | DOES NOT ALLOW CONTINUOUS PAPER FLOW. PER WPB FBC |
| | 107.2.1, INDICATE THE SAME. |
| | 8. RE: PLAN SHEET A-2.1.1; DETAIL 9. PER FBC ACC 604.2, |
| | PER FBC ACC 604.5.1, THE SIDE WALL GRAB BAR SHALL BE 42 |
| | INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305 |
| | MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES |
| | (1370 MM) MINIMUM FROM THE REAR WALL. PER WPB FBC |
| | 107.2.1, INDICATE THE SAME. |
| | 9. RE: PLAN SHEET A-2.1.1; DETAIL 10. PER WPB FBC |
| | 107.2.1, TO COMPLY WITH FBC ACC 306.3.1, PROVIDE |
| | MINIMUM 27 INCHES ABOVE THE FLOOR FOR KNEE CLEARANCE. |
| | 10. RE: PLAN SHEET P2.01; CHRONOMITE CM-15L/120 |
| | TANKLESS WATER HEATER IS DESIGNED TO DELIVER .5 GPM, |
| | WHICH IS ADEQUATE FOR THE LAVATORY BUT APPEARS NOT TO |
| | PROPERLY ACCOMMODATE THE SINK. PER WPB FBC 107.2.1, |
| | PLEASE REVISIT AND CONFIRM OR MAKE CORRECTIONS AS |
| | REQUIRED. PROVIDE SPECIFICATIONS FOR EACH WATER HEATER. |
| | 11. RE: PLAN SHEET P2.01; TEMPERED WATER SHALL BE |
| | DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES |
| | LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR |
| | CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL |
| | BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3 PER FBC PL 416.5. PER WPB FBC 107.2.1, INDICATE |
| | THE SAME. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19110420 251 BANYAN BLVD |
| | |