Plan Review Notes
Plan Review Notes For Permit 19110420
Permit Number 19110420
Review Stop B
Sequence Number 1
Notes
Date Text
2019-11-16 06:42:052017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110420
 ADD: 251 BANYAN BLVD.
 CONT: TYCON MANAGEMENT LLC
 TEL: 561-860-1663
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. NOV. 16/ 2019
 ACTION: DENIED
  
 1) ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
 2) SHEET A2.1.1.:
  
 2A) RESTROOM DETAILS 8 & 9 BOTH SHOW THE WATER CLOSET
 GRAB RAILS BEING MEASURED 36 INCHES FROM THE CENTERLINE
 OF THE GRAB BAR ABOVE THE FLOOR LEVEL. PLEASE NOTE IN
 THE 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION
 OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
 A 36 INCH MEASUREMENT MEASURED FROM THE CENTERLINE ON A
 1 ? GRAB BAR WOULD PUT THE GRAB BAR 36 ? INCHES ABOVE
 THE FINISH FLOOR BECAUSE OF THE MEASURING FROM CENTER
 LINE AND NOT THE TOP OF THE GRIPPING SURFACE.
  
 2B) DETAIL 9 OF THE SAME PAGE, IT APPEARS EITHER THE
 DETAIL WAS PARTIALLY DELETED OR THE PRINTER RAN OUT OF
 INK IN THE SAME AREA ON BOTH SETS OF PLANS? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2C) DISCREPANCY IN PLANS. PLEASE REVIEW DETAILS B
 RESTROOM 113 AND DETAIL 8. IN DETAIL B THE WATER CLOSET
 IS DIMENSIONED (BACKWALL) 1 FOOT 6 INCHES AWAY FROM THE
 NEAREST CORNER WHEREAS IN THE DETAIL 8 THE WATER CLOSET
 IS DIMENSIONED AT 1 FOOT 5 INCHES, A DISCREPANCY OF 1
 INCH. THE CODE DOES ALLOW THE ACCESSIBLE WATER CLOSET
 TO BE BETWEEN 16-18 INCHES AWAY FROM THE CORNER WALL
 (2017 ACCESSIBILITY CODE SECTION 604.2 LOCATION).
 PLEASE CORRECT THE DISCREPANCY IN THE PLANS. 107.2.1.2
 ADDITIONAL INFORMATION REQUIRED, DISCREPANCY.
  
 2D) DETAIL A BREAK ROOM CABINETRY. THE FLOOR PLAN DOES
 NOT SHOW WHICH APPROACH WILL BE USED TO GAIN ENTRY TO
 THE BREAK ROOM SINK. THE LOCATION OF THE REQUIRED
 ACCESSIBLE SINK GIVEN ON THIS PLAN APPEARS TO
 CENTERLINE 18 INCHES FROM THE CORNER WALL. SHEET
 A4.1.1. DETAIL 9 A SECTION OF THE SAME CABINETRY SHOWS
 A TOE KICK AND BOTTOM IN THE CABINETRY AND THE PIPES
 NOT COVERED WITH INSULATION. IT APPEARS AS DRAWN
 NEITHER A SIDE APPROACH NOR FRONT APPROACH WILL WORK.
 PLEASE PROVIDE COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTIONS:
  
 602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER LAVATORIES AND SINKS.
  
 MUST ALSO COMPLY WITH 306.2 TOE CLEARANCE AND 306.3
 KNEE CLEARANCE FOR FORWARD APPROACH. 2017
 FBC-ACCESSIBILITY CODE.
  
 IN THE PRESENT LOCATION A SIDE APPROACH WILL NOT WORK,
 THE CENTERLINE OF THE SINK WOULD BE REQUIRED TO BE 2
 FEET FROM THE CORNER WALL FOR THE SIDE APPROACH TO
 WORK.
  
  
 3) SHEET A1.1.1.WINDOW TYPES A & B BOTH QUALIFY AS
 GLAZING IN HAZARDOUS LOCATIONS SEE 2406.4.3 OF THE 2017
 FBC-B. PLEASE IDENTIFY WINDOWS AS SUCH AND THE TYPE OF
 TREATMENT TO BE USED ON THESE WINDOWS.
  
 4) SHEET A1.1.1. PLEASE PROVIDE WHERE THE PROPERTY LINE
 IS LOCATED SINCE THE ENTRY DOORS ARE A OUTSWING DOOR
 AND MAY SWING OUT OVER THE PROPERTY LINE? SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION:
  
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
 ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL
 BE PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS
 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT
 OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  