| Plan Review Notes For Permit 19110404 |
| Permit Number |
19110404 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-08 09:49:21 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ASPHALT SINGLE ROOF HAS A 3:12 SLOPE WHICH | | | REQUIRES A DOUBLE UNDERLAYMENT PER FBC-R905.2.2 | | | | | | 2) CLARIFY WHERE THE POLYGLASS UNDERLAYMENT WILL BE | | | USED. SPECIFY WHICH ONE OF THE UNDERLAYMENTS WILL BE | | | USED FOR THIS PROJECT. FBC107.2.1 | | | | | | 3) THE CERTAINTEED SELF-ADHEARED MODIFIED THAT WAS | | | SELECTED ON PAGE 11 OF PRODUCT APPROVAL W-4 HAS A | | | MAXIMUM DESIGN PRESSURE OF -60 PSF. THIS IS TO LOW FOR | | | THE ROOF CORNERS. FBCR-301.2.1 |
|