| 2020-06-22 12:16:41 | 4TH REVIEW FBC-2017 MECHANICAL |
| | PERMIT-19110402 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE GAS PRESSURE DELIVERED TO THE |
| | METER. IF THIS IS A 2PSI SYSTEM PLEASE SHOW THE |
| | REGULATOR LOCATION THAT STEPS THE PRESSURE DOWN. |
| | PROVIDE THE SPECS ON ALL REGULATORS USED IN THIS |
| | INSTALLATION. FBC FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE THE BTU?S ON THE DRAWING FOR THE NEW |
| | GENERATOR. FBC FS 107.2.1 |
| | |
| | 3) PLEASE SHOW A DETAIL OF THE NEW PIPING CONNECTING TO |
| | THE EXISTING PIPING SYSTEM. FBC FS 107.2.1 |
| | |
| | 4) THE ?? GALV. PIPE FROM THE METER TO THE ?T? |
| | CONNECTION FOR THE NEW PIPING TO THE GENERATOR MUST BE |
| | ABLE TO CARRY THE ENTIRE PIPING SYSTEM BTU?S AT THE NOW |
| | LONGER ? LONGEST LENGTH METHOD?. FBC FS 107.2.1 |
| | |
| | 5) PROVIDE THE NUMBERS OF THE GAS TABLES USED TO SIZE |
| | THIS SYSTEM. FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |