| 2020-01-02 11:04:37 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING - COMMENT FROM FIRST REVIEW WAS NOT | | | ADDRESSED. | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD AND ANCHORING PLANS FROM AN | | | ENGINEER ARE REQUIRED TO HAVE THE ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATIRE. ENGINEERING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH MUST | | | BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE | | | PROVISIONS OF SECTION 471.025, F.S., AND RULE | | | 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED | | | AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL | | | ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | | USED. | | | |
|