| Plan Review Notes For Permit 19110365 |
| Permit Number |
19110365 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-12-12 12:13:30 | PLUMBING COMMENTS: APPROVED W/PROVISO | | | REFER TO PLAN SHEET A-2; PLUMBING RISER | | | 1. REMOVE PROHIBITED HORIZONTAL DRY VENT AT WATER | | | CLOSET PER FBC RES P3104.3 AND P3104.4. | | | 2. VENT FOR WATER CLOSET NOT REQUIRED PER FBC RES | | | P3108.1. REMOVE AS IT IS CONNECTED TO PROHIBITED | | | HORIZONTAL DRY VENT. | | | 3. MAXIMUM DEVELOPED LENGTH OF SHOWER DRAIN TRAP TO | | | VENT SHALL BE 8 FEET-0 INCHES PER FBC RES TABLE P3105.1 | | | 4. WATER CLOSET AND SHOWER FIXTURE DRAINS CONNECT | | | INDEPENDENTLY TO THE WET VENT PER FBC RES P3108.1 | | | 5. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | | INSPECTOR'S APPROVAL | | | | | | |
|