| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.2 STANDARD |
| | ROLL-IN TYPE SHOWER COMPARTMENTS. IN STANDARD ROLL-IN |
| | TYPE SHOWER COMPARTMENTS, THE CONTROLS, FAUCETS, AND |
| | SHOWER SPRAY UNIT SHALL BE LOCATED ABOVE THE GRAB BAR, |
| | BUT NO HIGHER THAN 48 INCHES ABOVE THE SHOWER FLOOR. |
| | WHERE A SEAT IS PROVIDED, THE CONTROLS, FAUCETS, AND |
| | SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE BACK WALL |
| | ADJACENT TO THE SEAT WALL AND SHALL BE LOCATED 27 |
| | INCHES MAXIMUM FROM THE SEAT WALL. AND |
| | 608.6 SHOWER SPRAY UNIT AND WATER. A SHOWER SPRAY UNIT |
| | WITH A HOSE 59 INCHES LONG MINIMUM THAT CAN BE USED |
| | BOTH AS A FIXED-POSITION SHOWER HEAD AND AS A HAND-HELD |
| | SHOWER SHALL BE PROVIDED. THE SHOWER SPRAY UNIT SHALL |
| | HAVE AN ON/OFF CONTROL WITH A NON-POSITIVE SHUT-OFF. IF |
| | AN ADJUSTABLE-HEIGHT SHOWER HEAD ON A VERTICAL BAR IS |
| | USED, THE BAR SHALL BE INSTALLED SO AS NOT TO OBSTRUCT |
| | THE USE OF GRAB BARS. SHOWER SPRAY UNITS SHALL DELIVER |
| | WATER THAT IS 120?F (49?C) MAXIMUM |
| | |
| | 2. PROVIDE SHUT OF VALVE FOR ALL DOWN FED WATER LINE |
| | CAN BE ON THE BRANCH FROM MAIN LINE. PER FBC PL 606.1 |
| | (5) |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |