| 2020-02-07 12:53:50 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19110320 |
| | 11/21/19 |
| | |
| | CODE IN EFFECT: |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M - FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC - FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG - FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX - FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS - FLORIDA STATUTES |
| | FAC - FLORID ADMINISTRATIVE CODE |
| | WPB - WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | 1. PLEASE REFERE TO FLORIDA ADMINISTRATIVE CODE SECTION |
| | 59A-36.025 EMERGENCY ENVIRONMENTAL CONTROL FOR ASSISTED |
| | LIVING FACILITIES. A DETAILED EMERGENCY ENVIRONMENTAL |
| | CONTROL PLAN IS REQUIRED. I HAVE COPIED ITEM (1) AND |
| | (1) (A) OF THE SECTION BELOW. COMPLIANCE WITH ALL ITEMS |
| | LISTED UNDER THE SECTION IS REQUIRED. |
| | (1) DETAILED EMERGENCY ENVIRONMENTAL CONTROL PLAN. EACH |
| | ASSISTED LIVING FACILITY SHALL PREPARE A DETAILED PLAN |
| | ("PLAN") TO SERVE AS A SUPPLEMENT TO ITS COMPREHENSIVE |
| | EMERGENCY MANAGEMENT PLAN, TO ADDRESS EMERGENCY |
| | ENVIRONMENTAL CONTROL IN THE EVENT OF THE LOSS OF |
| | PRIMARY ELECTRICAL POWER IN THAT ASSISTED LIVING |
| | FACILITY WHICH INCLUDES THE FOLLOWING INFORMATION: |
| | (A) THE ACQUISITION OF A SUFFICIENT ALTERNATE POWER |
| | SOURCE SUCH AS A GENERATOR(S), MAINTAINED AT THE |
| | ASSISTED LIVING FACILITY, TO ENSURE THAT CURRENT |
| | LICENSEES OF ASSISTED LIVING FACILITIES WILL BE |
| | EQUIPPED TO ENSURE AMBIENT AIR TEMPERATURES WILL BE |
| | MAINTAINED AT OR BELOW 81 DEGREES FAHRENHEIT FOR A |
| | MINIMUM OF NINETY-SIX (96) HOURS IN THE EVENT OF THE |
| | LOSS OF PRIMARY ELECTRICAL POWER. |
| | (2) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING |
| | CODE AND PROVIDE MINIMUM VENTILATION CALCUATIONS FOR |
| | ALL ROOMS AND SPACES INVOLVED IN THE RENOVATION. SEE |
| | TABLE 403.3.1.1 FBC M AND PROVIDE A SCHEDULE THAT |
| | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR |
| | AIR. |
| | (3) PROVIDE DETAILS FOR INSTALLATION OF THE WALL AC |
| | UNITS - SECTION 310.15 FBC M. INSTALLATIONS SHALL BE IN |
| | GUIDELINES FOR HURRICANE ZONE INSTALLATIONS OR SITE |
| | SPECIFIC ENGINEERING SHALL BE PROVIDED. |
| | (4) SHEET M-2: PLEASE UPDATE THE CODE REFERENCES LISTED |
| | IN THE HVAC NOTES TO THE CURRENT APPLICABLE EDITIONS OF |
| | THE FBC, NFPA, SMACNA AND ASHRAE. |
| | (5) THE $40,000 PROJECT VALUE ON THE PERMIT APPLICATION |
| | APPEARS TO BE A LOW VALUE FOR THE SCOPE OF WORK SHOWN |
| | ON THE PLANS. PLEASE PROVIDE COPIES OF CONTRACTS, |
| | ESTIMATES, INVOICES, ETC. FOR THE ENTIRE SCOPE OF WORK |
| | INCLUDING ARCHITECTURAL, STRUCTURAL, MEP, SITE WORK, |
| | DESIGN FEES, OVERHEAD AND PROFIT. PLEASE NOTE VALUE IS |
| | BASED ON ALL COSTS ASSOCIATED WITH THE PROJECT |
| | INCLUDING LABOR, MATERIALS, EQUIPMENT, FIXTURES, |
| | APPLIANCES, ETC. |
| | |
| | WHEN RESUBMITTING IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |