Plan Review Notes
Plan Review Notes For Permit 19110260
Permit Number 19110260
Review Stop P
Sequence Number 3
Notes
Date Text
2020-03-05 11:12:111) THERE ARE TWO DIFFERENT GREAE INTERCEPTOR DETAILS ON
 SHT. C8.6. WHICH ONE IS BEING INSTALLED? CROSS OUT THE
 INTERCEPTOR WHICH WILL NOT BE USED. WPB AMEND. TO FBC
 SEC. 107.2.1.
 2) THERE IS A THIRD DETAIL FOR A GREASE INTERCEPTOR
 THAT HAS BEEN UPLOADED THAT IS FROM US CONCRETE
 PRODUCTS. IF THIS UNIT IS NOT BEING INSTALLED, DELETE
 IT FROM THIS SUBMITTAL PACKAGE.WPB AMEND. TO FBC SEC.
 107.2.1.
 AT THIS POINT, IT IS CONFUSING AS TO WHICH INTERCEPTOR
 IS BEING INSTALLED.
  