| 2020-01-07 09:07:19 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | NO ELECTRICAL RESPONSE PROVIDED. ONLY ONE SET OF PLANS |
| | IN SET, AND NO ELECTRICAL SHEETS IN THAT SET. PROVIDE |
| | TWO COPIES OF PLAN FOR REVIEW, AND ANSWER PREVIOS |
| | COMMENTS. WPB FBC 107.2.1 |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 |
| | 2. PLAN STATES RECEPTACLES MARKED TP ARE TO BE TAMPER |
| | PROOF, AND THEN SOME OF THE OUTLETS ARE MARKED TR, BUT |
| | NOT ALL OF THEM. PROVIDE CORRECTION. EACH RECEPTACLE |
| | DOES NOT HAVE TO BE MARKED, A NOTE WILL SUFFICE THAT |
| | ALL RECEPTACLE OUTLETS MUST BE TAMPER RESISTANT. NEC |
| | 406.12; FBC RE E4002.14 |
| | 3. PROVIDE ACCURATE LOAD CALCULATION PER THE METHOD |
| | PRESCRIBED IN FBC RESIDENTIAL. NEC 220; FBC RE E3602.2 |
| | 4. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| | 5. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 |
| | 6. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS |
| | FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS |
| | SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE |
| | IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A |
| | RECEPTACLE OUTLET IN THAT SPACE, AND SHOULD BE |
| | INSTALLED IN EACH LOCATION WHERE THE COUNTER TOP IS 12 |
| | INCHES OR GREATER. THE PLAN PROVIDED DOES NOT MEET THIS |
| | CODE IN SOME AREAS. PROVIDE CORRECTION. NEC |
| | 210.52(C)(1); FBC RE E3901 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |