| 2019-11-25 13:41:53 | ALTERATION BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | PERMIT #19110249 |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1- USE OF THIS BUILDING IS NOT CLEAR. PLANS SHOW THE |
| | LAYOUT OF A SINGLE FAMILY RESIDENCE BUT ALL THE |
| | INFORMATION SHOWN UNDER THE AREA CALCULATIONS IS FOR |
| | BUSINESS TYPE USE. CLARIFY/REVISE AS REQUIRED. CLEARLY |
| | DEFINE THE USE OF THE BUILDING. SEC. 107.2.1 CITY |
| | AMENDMENTS AND SEC. 301.1 FBC-BUILDING. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. 811.1 FBC-EXISTING BUILDING. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 3-CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM |
| | WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY |
| | COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 |
| | FBC-EXISTING BUILDING. |
| | NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD |
| | SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR |
| | EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE |
| | EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY |
| | SEC. 702.5. |
| | |
| | 4-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| | DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |