| Plan Review Notes For Permit 19110237 |
| Permit Number |
19110237 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-16 10:52:31 | PERMIT #19110237 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ELEVATOR REHABILITATION | | | 43.6.6 ELEVATORS. IN HIGH-RISE BUILDINGS, WHERE THE | | | REHABILITATION | | | WORK AREA IS ONE ENTIRE FLOOR, OR WHERE THE | | | REHABILITATION | | | WORK AREA IS 20 PERCENT OR MORE OF THE OCCUPIED FLOOR | | | AREA OF THE | | | BUILDING, ALL FLOORS SHALL BE ACCESSIBLE BY AT LEAST | | | ONE ELEVATOR. | | | | | | ELEVATOR RECALL SHALL COMPLY WITH NFPA 72, NFPA 101 | | | | | | 1. WHAT IS THE OPERATIONS OF THE ELEVATION | | | PREDETERMINED LEVEL UPON ACTIVATION? | | | | | | 2. UNDER SCOPE OF WORK IT STATES THAT SYSTEM WILL BE | | | LOCAL AND INDEPENDENT OF THE EXISTING BUILDING'S FIRE | | | ALARM. | | | 21.3.1 ALL INITIATING DEVICES USED TO INITIATE FIRE | | | FIGHTERS SERVICE | | | RECALL SHALL BE CONNECTED TO THE BUILDING FIRE ALARM | | | SYSTEM. | | | | | | 3.3.105.4.1 BUILDING FIRE ALARM SYSTEM. A PROTECTED | | | PREMISES | | | FIRE ALARM SYSTEM THAT INCLUDES ANY OF THE FEATURES | | | IDENTIFIED IN 23.3.3.1 AND THAT SERVES THE GENERAL FIRE | | | ALARM | | | NEEDS OF A BUILDING OR BUILDINGS AND THAT PROVIDES FIRE | | | DEPARTMENT | | | OR OCCUPANT NOTIFICATION OR BOTH. (SIG-PRO) | | | | | | | | | | | | BRITTANY WOODS | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4754 | | | | | | |
|