2019-11-16 10:52:31PERMIT #19110237
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ELEVATOR REHABILITATION
 43.6.6 ELEVATORS. IN HIGH-RISE BUILDINGS, WHERE THE
 REHABILITATION
 WORK AREA IS ONE ENTIRE FLOOR, OR WHERE THE
 REHABILITATION
 WORK AREA IS 20 PERCENT OR MORE OF THE OCCUPIED FLOOR
 AREA OF THE
 BUILDING, ALL FLOORS SHALL BE ACCESSIBLE BY AT LEAST
 ONE ELEVATOR.
  
 ELEVATOR RECALL SHALL COMPLY WITH NFPA 72, NFPA 101
  
 1. WHAT IS THE OPERATIONS OF THE ELEVATION
 PREDETERMINED LEVEL UPON ACTIVATION?
  
 2. UNDER SCOPE OF WORK IT STATES THAT SYSTEM WILL BE
 LOCAL AND INDEPENDENT OF THE EXISTING BUILDING'S FIRE
 ALARM.
 21.3.1 ALL INITIATING DEVICES USED TO INITIATE FIRE
 FIGHTERS SERVICE
 RECALL SHALL BE CONNECTED TO THE BUILDING FIRE ALARM
 SYSTEM.
  
 3.3.105.4.1 BUILDING FIRE ALARM SYSTEM. A PROTECTED
 PREMISES
 FIRE ALARM SYSTEM THAT INCLUDES ANY OF THE FEATURES
 IDENTIFIED IN 23.3.3.1 AND THAT SERVES THE GENERAL FIRE
 ALARM
 NEEDS OF A BUILDING OR BUILDINGS AND THAT PROVIDES FIRE
 DEPARTMENT
 OR OCCUPANT NOTIFICATION OR BOTH. (SIG-PRO)
  
  
  