| 2019-11-06 17:47:21 | 11/06/2019 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 2. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM PER THE 2017 FBC RES. SEC. G2413.3 |
| | 3. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC RES. SEC. G2401.1.3. |
| | 4. SHOW AND LABEL DRIP LEG ON EQUIPMENT INSTALLED PER |
| | THE 2017 FBC RES. SEC. G2419.2 OR 2017 FBC FG 408.2. |
| | 5. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, THE |
| | CORRESPONDING EHD NUMBER OF THE CORRUGATED |
| | STAINLESS-STEEL TUBING (IF APPLICABLE) FOR EACH PIPE |
| | SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | 6. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR, 2017 FBC RES. SEC. G2420.4. |
| | 7. YOU LISTED THE BTU'S LOAD OF EACH APPLIANCE IN THE |
| | INSIDE BUT PLEASE ADD THE TOTAL BTU LOAD ON THE SYSTEM |
| | FOR OUTSIDE GRILL TO TALLY A TOTAL. REFER TO THE 2017 |
| | FBC RES. SEC. G2413. |
| | 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | (CLOTHES DRYERS AND STOVE) 2017 FBC RES. SEC. G2407.1 |
| | AND G2439.4. WHERE IS COMBUSTION AIR PROVIDED BY THE |
| | BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017 |
| | FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR AND |
| | VENTILATION AIR SYSTEM. |
| | 9. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR (DRYER, STOVE AND GRILL) |
| | ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC |
| | RES. SEC. G2408.1. |
| | 10. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER |
| | A ROOF. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 11. TELL ME IF THE GRILL LABELED FOR OUTSIDE USE AND IF |
| | IT TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE |
| | MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD PER |
| | THE 2017 FBC RES. SEC. G2408.1. |
| | 12. IF USING STEP DOWN REGULATORS SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| | SEC. G2421.1. |
| | 13. IF APPLICABLE PLEASE SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC |
| | G2421.2. |
| | 15. THE TOTAL JOB COST SEEMS LOW. THE VALUE MUST |
| | INCLUDE THE COST OF ALL EQUIPMENT INCLUDING DYERS, |
| | GRILL AND STOVE. PROVIDE BONA FIDE SIGNED CONTRACT PER |
| | WPB AMENDMENTS TO THE FBC 109.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |