| Plan Review Notes For Permit 19110179 |
| Permit Number |
19110179 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-13 09:19:51 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NEED RISER DIAGRAM, SHOWING WIRE SIZES TO PANEL | | | | | | 2) PANEL DOES NOT APPEAR TO BE SERVICE ENTRANCE RATED. | | | PLEASE VERIFY. | | | | | | 3) TEMP DIAGRAM SHOWS 6' POLE IT NEEDS TO BE LONGER FOR | | | INSTALLATION IN THE GROUND. | | | | | | 4) PLANS DRAWN BY YOU NEED TO SIGNED BY YOU. |
|