| Notes |
| Date |
Text |
| 2019-11-22 08:26:21 | 1) SHT. 2 OF 5 APPEARS TO BE MISSING FROM BOTH SETS OF | | | PLANS. SUBMIT TWO COPIES OF SHT. 2 AND INSERT THE | | | SHEETS INTO THE SETS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHT. 3 OF 5 - "PLUMBING NOTES" - NOTE # 3 OF 5 | | | REFERS TO THE 2014 FBC. THE CODE IN EFFECT FOR THIS JOB | | | IS THE 2018 FBC-PLUMBING.WPB AMEND. TO FBC SEC.101.1. | | | 3) SHT.3 OF 5 - NOTE #10 REFERS TO AIR CHAMBERS ON THE | | | BATHROOM GROUPS. AIR CHAMBERS ARE NOT APPROVED FOR USE. | | | A WATER HAMMER ARRESTOR IS REQUIRED. 2017 FBC-PLUMBING | | | SEC. 604.9. | | | 4) SHT. 3 OF 5 - NOTE #16 - THE INSULATION ON THE HOT | | | WATER SYSTEM SHALL HAVE A MINIMUM R-3 THERMAL | | | RESISTANCE PER 2017 FBC- ENERGY, SEC. R403.5.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|