2019-11-14 15:24:001ST REVIEW FBC-2017 MECHANICAL
 SUBMITTAL #19110146
 DR. ALICE MOORE APARTMENTS
 PERMIT #18061140
 11/14/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AHRI CERTIFICATES: THE MODEL NUMBERS AND EFFICIENCY
 RATINGS DO NOT MATCH WITH THE AC EQUIPMENT SCHEDULE AND
 THE ENERGY CALCULATIONS. APPARENTLY LESS EFFICIENT
 SYSTEMS WILL BE INSTALLED. A REVISION TO THE PLANS AND
 CALCULATIONS WILL BE REQUIRED- SEE SHEET M-3.00.
  
 2) DRYER BOOSTER FAN: THE SELECTED FAN MODEL IS 120
 VOLT AND HAS LESS CFM CAPACITY (188 CFM) THAN THE MODEL
 SPECIFIED ON SHEET M-1.01 WHICH IS 208 VOLT (220 CFM).
 PLEASE REVISE THE MECHANICAL AND ELECTRICAL PLAN
 ACCORDINGLY.
  
 3) DRYERS: PROVIDE DATA ON INSTALLATION INSTRUCTION
 SHEETS THAT INDICATE THE MAXIMUM LENGTH OF THE EXHAUST
 DUCT RUNS FROM THE DRYER TO THE OUTLET- SECTION
  
 4) HVAC SHOP DRAWINGS: FULLL SIZE DRAWINGS ARE REQUIRED
 FOR REVIEW AND INSPECTION PURPOSES- SECTION 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  