| 2019-11-14 15:24:00 | 1ST REVIEW FBC-2017 MECHANICAL |
| | SUBMITTAL #19110146 |
| | DR. ALICE MOORE APARTMENTS |
| | PERMIT #18061140 |
| | 11/14/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) AHRI CERTIFICATES: THE MODEL NUMBERS AND EFFICIENCY |
| | RATINGS DO NOT MATCH WITH THE AC EQUIPMENT SCHEDULE AND |
| | THE ENERGY CALCULATIONS. APPARENTLY LESS EFFICIENT |
| | SYSTEMS WILL BE INSTALLED. A REVISION TO THE PLANS AND |
| | CALCULATIONS WILL BE REQUIRED- SEE SHEET M-3.00. |
| | |
| | 2) DRYER BOOSTER FAN: THE SELECTED FAN MODEL IS 120 |
| | VOLT AND HAS LESS CFM CAPACITY (188 CFM) THAN THE MODEL |
| | SPECIFIED ON SHEET M-1.01 WHICH IS 208 VOLT (220 CFM). |
| | PLEASE REVISE THE MECHANICAL AND ELECTRICAL PLAN |
| | ACCORDINGLY. |
| | |
| | 3) DRYERS: PROVIDE DATA ON INSTALLATION INSTRUCTION |
| | SHEETS THAT INDICATE THE MAXIMUM LENGTH OF THE EXHAUST |
| | DUCT RUNS FROM THE DRYER TO THE OUTLET- SECTION |
| | |
| | 4) HVAC SHOP DRAWINGS: FULLL SIZE DRAWINGS ARE REQUIRED |
| | FOR REVIEW AND INSPECTION PURPOSES- SECTION 107.2.1 |
| | WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |