2019-11-04 11:57:281ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19110122
 11/4/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PERMIT #19101297 WAS INCORRECTLY ISSUED AS AN AC
 CHANGEOUT, HOWEVER THE PALM BEACH COUNTY PROPERTY
 APPRAISOR'S REPORT LISTS NO EXISITNG HEATING OR AIR
 CONDITIONING. PLEASE PROVIDE THE FOLLOWING:
  
 A) AC COOLING AND HEATING CALCULATIONS- SECTION
 R403.7.1 FBC EC.
 B) ENERGY CALCULATIONS- SECTION R101.5.1.1 & R503.2 FBC
 RES
  
 2) PLEASE PROVIDE A COPY OF A SIGNED CONTRACT FOR THE
 COST OF THE NEW AC SYSTEM AND DUCTWORK- SECTION 109.3
 WPB.
  
 3) SHOW THE LOCATION OF THE NEW CONDENSER AND PROVIDE
 CONSTRUCTION DETAILS FOR THE NEW PAD, CONDENSER
 TIE-DOWN DETAILS PER SECTIONS M1305.1.4.1 AND M1401.4
 FBC RES.
  
 4) PROVIDE AN ELECTRICAL PLAN- SECTION 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  