| 2019-11-04 11:57:28 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19110122 |
| | 11/4/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PERMIT #19101297 WAS INCORRECTLY ISSUED AS AN AC |
| | CHANGEOUT, HOWEVER THE PALM BEACH COUNTY PROPERTY |
| | APPRAISOR'S REPORT LISTS NO EXISITNG HEATING OR AIR |
| | CONDITIONING. PLEASE PROVIDE THE FOLLOWING: |
| | |
| | A) AC COOLING AND HEATING CALCULATIONS- SECTION |
| | R403.7.1 FBC EC. |
| | B) ENERGY CALCULATIONS- SECTION R101.5.1.1 & R503.2 FBC |
| | RES |
| | |
| | 2) PLEASE PROVIDE A COPY OF A SIGNED CONTRACT FOR THE |
| | COST OF THE NEW AC SYSTEM AND DUCTWORK- SECTION 109.3 |
| | WPB. |
| | |
| | 3) SHOW THE LOCATION OF THE NEW CONDENSER AND PROVIDE |
| | CONSTRUCTION DETAILS FOR THE NEW PAD, CONDENSER |
| | TIE-DOWN DETAILS PER SECTIONS M1305.1.4.1 AND M1401.4 |
| | FBC RES. |
| | |
| | 4) PROVIDE AN ELECTRICAL PLAN- SECTION 109.3 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |