| Plan Review Notes For Permit 19110044 |
| Permit Number |
19110044 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-07 18:48:13 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE HANDRAIL EXTENSION AT THE BOTTOM OF THE STAIRS | | | SHOWN IN DETAIL 1 ON SHEET A-3.0.2 DOES NOT COMPLY WITH | | | THE CODE. THE DRAWING SHOWS A PORTION OF THE HANDRAIL | | | EXTENSION THAT IS LEVEL. FBC ACCESSIBILTY SECTION | | | 505.10.3. AT THE BOTTOM OF A STAIR FLIGHT, HANDRAILS | | | SHALL EXTEND AT THE SLOPE OF THE STAIR FLIGHT FOR A | | | HORIZONTAL DISTANCE AT LEAST EQUAL TO ONE TREAD DEPTH | | | BEYOND THE LAST RISER NOSING. EXTENSION SHALL RETURN TO | | | A WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE | | | CONTINUOUS TO THE HANDRAIL OF AN ADJACENT STAIR FLIGHT. | | | | | | | | | | | | | | | |
|