| 2019-12-09 14:03:04 | FAILED |
| | |
| | PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| | |
| | 1) REPEAT COMMENT: THE PLANS ARE EITHER REQUIRED TO |
| | HAVE THE CITYPLACE RETAIL, LLC, APPROVAL STAMP ON THEM, |
| | OR YOU MUST PROVIDE A SEPARATE LETTER FROM CITYPLACE |
| | RETAIL, LLC, APPROVING THE SPECIFIC PLANS THAT YOU HAVE |
| | SUBMITTED. |
| | |
| | 2) REPEAT COMMENT: SIGNAGE REQUIRES SEPARATE PERMIT |
| | WITH PLANS. NOTE: THE SIGNS DO NOT APPEAR TO CONFORM TO |
| | THE ROSEMARY SQUARE MASTER SIGN PLAN. |
| | |
| | 3) REPEAT COMMENT: THE 2ND LEVEL FLOOR PLAN INDICATE |
| | THAT THE EXTERIOR WALLS AT THE CORNER OF THE BAY, WHERE |
| | THE FITTING ROOMS ARE PROPOSED) ARE EXISTING SOLID |
| | WALLS (EXISTING STUCCO SURFACE FACADE ON SHEETS A200 |
| | AND A201). THIS IS NOT ACCURATE. THE OPENINGS HAVE A |
| | KNEE WALL WITH STOREFRONT GLAZING. THE EXISTING |
| | OPENINGS MAY NOT BE FILLED IN, BLACKED OUT OR OTHERWISE |
| | HAVE CONSTRUCTION TO OBSTRUCT THE VIEW INTO THE STORE. |
| | |
| | 4) REPEAT COMMENT: IT APPEARS THAT THERE IS NEW |
| | EQUIPMENT BEING INSTALLED ON THE ROOF. IN ACCORDANCE |
| | WITH THE CITYPLACE DRI, PLEASE PROVIDE VERIFICATION |
| | THAT ALL ROOFTOP MECHANICAL EQUIPMENT, INCLUDING BUT |
| | NOT LIMITED TO SUCH ITEMS AS PUBLIC AND PRIVATE UTILITY |
| | SERVICE CONNECTIONS; HEATING, VENTILATING, AND AIR |
| | CONDITIONING SYSTEMS; COMMUNICATIONS DEVICES; AND |
| | RELATED EQUIPMENT, SHALL BE SCREENED FROM PUBLIC VIEW |
| | THROUGH ANY COMBINATION OF LANDSCAPING, WALLS AND |
| | EQUIPMENT LOCATION. PLEASE PROVIDE PLANS OR OTHER |
| | EVIDENCE THAT THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL |
| | BE SCREENED FROM PUBLIC VIEW. |
| | |