Plan Review Notes
Plan Review Notes For Permit 19110041
Permit Number 19110041
Review Stop P
Sequence Number 2
Notes
Date Text
2019-12-17 19:23:052ND PLUMBING REVIEW**DENIED** COMMENTS FROM 1ST REVIEW
 HAVE NOT BEEN ADDRESSED. FAILURE TO FULLY COMPLY ON THE
 NEXT SUBMITTAL COULD LEAD TO A 4X PLAN REVIEW FEE.
 553.80 (B)?WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
 1) SHOW ELEVATOR SUMP PUMP AND DISCHARGE CHARGE PIPING.
 FBC 107.3.5
 2) SHT. G100 LIST THE AMENDMENTS YEAR AS 2010. PLEASE
 CORRECT AND LIST 2017. FBC 107.2.1
 3) SHOW BREAK ROOM SINK AS HAVING CLEAR FLOOR SPACE
 MATCHING ALL SHEETS THAT SHOW TOILET ROOM CLEAR FLOOR
 SPACE. FBC 107.3.5
 4) SHOW SEPARATE CLEAR FLOOR SPACE OUTSIDE THE ARC OF
 THE DOOR SWING AS REQUIRED IN FBC-ACC 603.2.3
 5) SHT. A-555 SHOW THE REAR GRAB BAR AS MOUNTING 12?
 FROM THE CENTER OF TOILET OVER TOWARDS THE SIDE WALL.
 FBC-ACC 604.5.2
 6) SHOW HOT WATER RETURN LINE AS IT APPEARS THE
 DISTANCE EXCEEDS THE MAX ALLOWED FROM THE SOURCE OF HOT
 WATER. FBC-ENERGY C404.5.1, FBC-PLB 607.2
 7) CALL OUT MIN ALLOWED PIPE INSULATIONS IS 1? WALL.
 SHT. P400 CALLS OUT ALL PIPING 2? AND UNDER MIN 1?
 WALL. SEE TABLE C403.2.10 FBC 107.2.1
 8) SHT.P-200 DETAIL (D) CALLS OUT WATER HEATER IS POINT
 OF USE BUT SHOW TANK TYPE. PLEASE CLARIFY. FBC-107.2
 9) PROVIDE WATER HEATER INSTALLATION MANUAL SHOW IT
 COMPLIES WITH MIN ENERGY REQUIREMENTS. FBC-ENERGY
 C404.2
 TIM HUNT
 PLUMBING PLAN EXAMINER
 CITY OF WEST PALM BEACH ( CGA SOLUTIONS)