| 2019-12-17 19:23:05 | 2ND PLUMBING REVIEW**DENIED** COMMENTS FROM 1ST REVIEW |
| | HAVE NOT BEEN ADDRESSED. FAILURE TO FULLY COMPLY ON THE |
| | NEXT SUBMITTAL COULD LEAD TO A 4X PLAN REVIEW FEE. |
| | 553.80 (B)?WITH RESPECT TO EVALUATION OF DESIGN |
| | PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS |
| | IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE |
| | FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| | REVIEW. |
| | |
| | 1) SHOW ELEVATOR SUMP PUMP AND DISCHARGE CHARGE PIPING. |
| | FBC 107.3.5 |
| | 2) SHT. G100 LIST THE AMENDMENTS YEAR AS 2010. PLEASE |
| | CORRECT AND LIST 2017. FBC 107.2.1 |
| | 3) SHOW BREAK ROOM SINK AS HAVING CLEAR FLOOR SPACE |
| | MATCHING ALL SHEETS THAT SHOW TOILET ROOM CLEAR FLOOR |
| | SPACE. FBC 107.3.5 |
| | 4) SHOW SEPARATE CLEAR FLOOR SPACE OUTSIDE THE ARC OF |
| | THE DOOR SWING AS REQUIRED IN FBC-ACC 603.2.3 |
| | 5) SHT. A-555 SHOW THE REAR GRAB BAR AS MOUNTING 12? |
| | FROM THE CENTER OF TOILET OVER TOWARDS THE SIDE WALL. |
| | FBC-ACC 604.5.2 |
| | 6) SHOW HOT WATER RETURN LINE AS IT APPEARS THE |
| | DISTANCE EXCEEDS THE MAX ALLOWED FROM THE SOURCE OF HOT |
| | WATER. FBC-ENERGY C404.5.1, FBC-PLB 607.2 |
| | 7) CALL OUT MIN ALLOWED PIPE INSULATIONS IS 1? WALL. |
| | SHT. P400 CALLS OUT ALL PIPING 2? AND UNDER MIN 1? |
| | WALL. SEE TABLE C403.2.10 FBC 107.2.1 |
| | 8) SHT.P-200 DETAIL (D) CALLS OUT WATER HEATER IS POINT |
| | OF USE BUT SHOW TANK TYPE. PLEASE CLARIFY. FBC-107.2 |
| | 9) PROVIDE WATER HEATER INSTALLATION MANUAL SHOW IT |
| | COMPLIES WITH MIN ENERGY REQUIREMENTS. FBC-ENERGY |
| | C404.2 |
| | TIM HUNT |
| | PLUMBING PLAN EXAMINER |
| | CITY OF WEST PALM BEACH ( CGA SOLUTIONS) |
| | [email protected] |
| | 561-248-2703 |
| | |