| 2019-11-18 14:37:33 | FAILED |
| | |
| | 1) THE PLANS ARE EITHER REQUIRED TO HAVE THE CITYPLACE |
| | RETAIL, LLC, APPROVAL STAMP ON THEM, OR YOU MUST |
| | PROVIDE A SEPARATE LETTER FROM CITYPLACE RETAIL, LLC, |
| | APPROVING THE SPECIFIC PLANS THAT YOU HAVE SUBMITTED. |
| | |
| | 2) SIGNAGE REQUIRES SEPARATE PERMIT WITH PLANS. NOTE: |
| | THE SIGNS DO NOT APPEAR TO CONFORM TO THE ROSEMARY |
| | SQUARE MASTER SIGN PLAN. |
| | |
| | 3) THE 2ND LEVEL FLOOR PLAN INDICATE THAT THE EXTERIOR |
| | WALLS AT THE CORNER OF THE BAY, WHERE THE FITTING ROOMS |
| | ARE PROPOSED) ARE EXISTING SOLID WALLS (EXISTING STUCCO |
| | SURFACE FA?ADE ON SHEETS A200 AND A201). THIS IS NOT |
| | ACCURATE. THE OPENINGS HAVE A KNEE WALL WITH STOREFRONT |
| | GLAZING. THE EXISTING OPENINGS MAY NOT BE FILLED IN, |
| | BLACKED OUT OR OTHERWISE HAVE CONSTRUCTION TO OBSTRUCT |
| | THE VIEW INTO THE STORE. |
| | |
| | 4) IT APPEARS THAT THERE IS NEW EQUIPMENT BEING |
| | INSTALLED ON THE ROOF. IN ACCORDANCE WITH THE CITYPLACE |
| | DRI, PLEASE PROVIDE VERIFICATION THAT ALL ROOFTOP |
| | MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH |
| | ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE |
| | CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING |
| | SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, |
| | SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY |
| | COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT |
| | LOCATION. PLEASE PROVIDE PLANS OR OTHER EVIDENCE THAT |
| | THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL BE SCREENED |
| | FROM PUBLIC VIEW. |
| | |