| Plan Review Notes For Permit 19110041 |
| Permit Number |
19110041 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-12 07:18:54 | 1ST PLUMBING REVIEW**DENIED** | | | | | | 1) SHOW ELEVATOR SUMP PUMP AND DISCHARGE CHARGE PIPING. | | | FBC 107.3.5 | | | 2) SHT. G100 LIST THE AMENDMENTS YEAR AS 2010. PLEASE | | | CORRECT AND LIST 2017. FBC 107.2.1 | | | 3) SHOW BREAK ROOM SINK AS HAVING CLEAR FLOOR SPACE | | | MATCHING ALL SHEETS THAT SHOW TOILET ROOM CLEAR FLOOR | | | SPACE. FBC 107.3.5 | | | 4) SHOW SEPARATE CLEAR FLOOR SPACE OUTSIDE THE ARC OF | | | THE DOOR SWING AS REQUIRED IN FBC-ACC 603.2.3 | | | 5) SHT. A-555 SHOW THE REAR GRAB BAR AS MOUNTING 12? | | | FROM THE CENTER OF TOILET OVER TOWARDS THE SIDE WALL. | | | FBC-ACC 604.5.2 | | | 6) SHOW HOT WATER RETURN LINE AS IT APPEARS THE | | | DISTANCE EXCEEDS THE MAX ALLOWED FROM THE SOURCE OF HOT | | | WATER. FBC-ENERGY C404.5.1, FBC-PLB 607.2 | | | 7) CALL OUT MIN ALLOWED PIPE INSULATIONS IS 1? WALL. | | | FBC 107.2.1 | | | 8) SHT.P-200 DETAIL (D) CALLS OUT WATER HEATER IS POINT | | | OF USE BUT SHOW TANK TYPE. PLEASE CLARIFY. FBC-107.2 | | | 9) PROVIDE WATER HEATER INSTALLATION MANUAL SHOW IT | | | COMPLIES WITH MIN ENERGY REQUIREMENTS. FBC-ENERGY | | | C404.2 | | | TIM HUNT | | | PLUMBING PLAN EXAMINER | | | CITY OF WEST PALM BEACH ( CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|