Plan Review Notes
Plan Review Notes For Permit 19110041
Permit Number 19110041
Review Stop P
Sequence Number 1
Notes
Date Text
2019-11-12 07:18:541ST PLUMBING REVIEW**DENIED**
  
 1) SHOW ELEVATOR SUMP PUMP AND DISCHARGE CHARGE PIPING.
 FBC 107.3.5
 2) SHT. G100 LIST THE AMENDMENTS YEAR AS 2010. PLEASE
 CORRECT AND LIST 2017. FBC 107.2.1
 3) SHOW BREAK ROOM SINK AS HAVING CLEAR FLOOR SPACE
 MATCHING ALL SHEETS THAT SHOW TOILET ROOM CLEAR FLOOR
 SPACE. FBC 107.3.5
 4) SHOW SEPARATE CLEAR FLOOR SPACE OUTSIDE THE ARC OF
 THE DOOR SWING AS REQUIRED IN FBC-ACC 603.2.3
 5) SHT. A-555 SHOW THE REAR GRAB BAR AS MOUNTING 12?
 FROM THE CENTER OF TOILET OVER TOWARDS THE SIDE WALL.
 FBC-ACC 604.5.2
 6) SHOW HOT WATER RETURN LINE AS IT APPEARS THE
 DISTANCE EXCEEDS THE MAX ALLOWED FROM THE SOURCE OF HOT
 WATER. FBC-ENERGY C404.5.1, FBC-PLB 607.2
 7) CALL OUT MIN ALLOWED PIPE INSULATIONS IS 1? WALL.
 FBC 107.2.1
 8) SHT.P-200 DETAIL (D) CALLS OUT WATER HEATER IS POINT
 OF USE BUT SHOW TANK TYPE. PLEASE CLARIFY. FBC-107.2
 9) PROVIDE WATER HEATER INSTALLATION MANUAL SHOW IT
 COMPLIES WITH MIN ENERGY REQUIREMENTS. FBC-ENERGY
 C404.2
 TIM HUNT
 PLUMBING PLAN EXAMINER
 CITY OF WEST PALM BEACH ( CGA SOLUTIONS)
 [email protected]
 561-248-2703
  