| 2019-11-18 16:48:24 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19110041 |
| | 11/18/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PLANS INDICATE THE NEW FCU'S UNDER A SEPARATE |
| | PERMIT, HOWEVER CURRENTLY THERE IS NO PERMIT APPLIED |
| | FOR, OR ISSUED FOR THE UNITS. PLEASE PROVIDE MORE |
| | INFORMATION, AND NOTE THAT SIZING CALCULATIONS MAY BE |
| | REQUIRED UNDER THIS PERMIT AND AN INCREASE IN VALUE FOR |
| | THE COST OF THE UNITS- SECTION 107.2.1 & 109.3 WPB. |
| | |
| | 2) SHEET M101: EXHAUST VENTILATION AT A RATE OF 0.25 |
| | CFMS PER SF. IS REQUIRED FOR THE FITTING ROOMS PER |
| | TABLE 403.3.1.1 FBC M. PLEASE REVISE THE PLANS |
| | ACCORDINGLY. |
| | |
| | 3) M101: THE CORRIDOR (HALLWAY) CANNOT BE USED TO |
| | RETURN AIR FROM THE ROOMS TO THE MECHANICAL ROOM- |
| | SECTION 601.2 FBC M. |
| | |
| | 4) M101: CLARIFY THE NEED FOR THE EXHAUST FANS EF-1 & 2 |
| | IN THE VISUAL AND OFFICE ROOMS. PROVIDE FAN SIZING |
| | CALCULATIONS AND THE SEQUENCES OF OPERATION- SECTION |
| | 107.2.1 WPB. |
| | |
| | 5) M300: THE ROOF MOUNTED FAN DETAIL IS INCOMPLETE. |
| | INDICATE HOW THE CURB WILL BE ATACHED TO THE STRUCTURE, |
| | AND THE FAN ATTACHED TO THE CURB. WHICH TYPE OF ANCHORS |
| | AND FASTENERS WILL BE USED- SECTION 301.15 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |