| 2019-11-20 11:34:58 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PLANS ARE REQUIRED TO BE APPROVED BY CITY PLACE |
| | MANAGEMENT. THE CITY PLACE APPROVAL STAMP IS REQUIRED |
| | TO BE ON THE DRAWINGS. |
| | |
| | 2) EXTERIOR SIGNS WILL REQUIRE A SEPARATE PERMIT. FBC |
| | 105.1 |
| | |
| | 3) A SEPARATE ROOFING REPAIR PERMIT WILL BE REQUIRED TO |
| | PATCH THE ROOF AT THE SKYLIGHT AND RELOCATED EQUIPMENT. |
| | FBC 105.1 |
| | |
| | 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR THE SKYLIGHT. |
| | |
| | 5) PLEASE REVISE THE CODE INFORMATION ON THE |
| | COVERSHEET. THE 2017 CHAPTER 1 AMENDMENTS SHOULD BE |
| | REFERENCED AND NOT THE 2010. |
| | |
| | 6) THE OCCUPANT LOAD FACTOR FOR THE GROUND FLOOR SALES |
| | AREA OF 30 GROSS IS INCORRECT. THE OCCUPANT LOAD FACTOR |
| | FOR MERCANTILE IS 60 GROSS PER FBC 2017 TABLE 1004.1.2. |
| | THIS WAS CHANGED FROM THE 2014 FBC. |
| | |
| | 7) THE ACCESSIBLE FITTING ROOM BENCH HEIGHT IS |
| | SPECIFIED AS 1'-6" AFF ON SHEET A450 AND 1'-7" ON SHEET |
| | A526. PLEASE COORDINATE. FBC 107.2.1 |
| | |
| | 8) ON SHEET A101, THERE IS A ROOM LABELED "VISUAL" WITH |
| | ONE HOUR FIRE RATED WALLS AND A 60 MINUTE FIRE RATED |
| | DOOR. PLEASE EXPLAIN THE USE OF THIS ROOM AND IDENTIFY |
| | THE TYPE AND QUANTITIES OF ANY HAZARDOUS MATERIALS THAT |
| | MAY BE PRESENT. FBC 107.2.1 AND 107.2.1.2 |
| | |
| | 9) THE LIFE SAFETY PLANS ARE NOT COMPLETE. THE LIFE |
| | SAFETY PLANS NEED TO SHOW THE FOLLOWING: |
| | A) NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1 |
| | B) CUMULATIVE OCCUPANT LOADS FBC 1004.1.1 |
| | C) EXIT SEPARATION DISTANCE FBC 1015.2.1 |
| | D) COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3 |
| | E) EXIT ACCESS TRAVEL DISTANCE FBC 1016.3 |
| | F) CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC |
| | 1008.1.1 |
| | G) CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED AND |
| | MEANS OF EGRESS FACTOR FBC1005.3.2 |
| | H) DISTRIBUTION OF EGRESS CAPACITY FBC1005.5 |
| | |
| | 10) WELDED OR BOLTED CONNECTIONS |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 2017 FBC-B 2204.2 BOLTING. |
| | |
| | 11) SUBMIT SHOP DRAWINGS FOR THE STAIRS FROM THE |
| | DELEGATE ENGINEER THAT HAVE BEEN REVIEWED AND APPROVED |
| | BY THE DESIGNER OF RECORD. FAC 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 12) SUBMIT SHORING PLANS FOR THE OPENING FOR THE NEW |
| | STAIRS THAT HAVE BEEN REVIEWED AND APPROVED BY THE |
| | DESIGNER OF RECORD. FAC 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 13) THE STRUCTURAL GENERAL NOTES ON SHEET S000 REQUIRE |
| | A REGISTERED ENGINEER OR TEST AGENCY WITH EXPERIENCED |
| | TECHNICIANS UNDER THE DIRECT SUPERVISION OF A |
| | REGISTERED ENGINEER TO PERFORM THE DUTIES OF THE |
| | SPECIAL INSPECTOR FOR THE STRUCTURAL INSPECTIONS. 2017 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| | INSPECTIONS SERVICES. RESIDENT INSPECTOR. THE BUILDING |
| | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE |
| | INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT |
| | REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION |
| | SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS |
| | SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A |
| | CERTIFICATE CALLED FOR BY ANY PROVISION OF THE |
| | TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS |
| | UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A |
| | RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 |
| | POUNDS PER SQUARE INCH |
| | 4. FOR PILE DRIVING |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES |
| | NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT. FOR |
| | THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME'. PLEASE CONTACT ME WITH AN EMAIL |
| | ADDRESS AND I WILL BE HAPPY TO SEND YOU A COPY OF THE |
| | OCTOBER 2018 GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT |
| | INSPECTORS. |
| | |
| | 14) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |