| 2019-11-05 10:24:34 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE ORIGINAL PLAN SUBMISSIONS FOR THIS PERMIT WERE |
| | IN DIGITAL FORMAT. FOR RECORD KEEPING PURPOSES, ANY |
| | REVISION SUBMITTED MUST ALSO BE IN DIGITAL FORMAT. |
| | PROVIDE CORRECTION. WPB FBC 107.1 |
| | 2. THE PANEL SCHEDULE FOR PANEL B STATES THAT THERE IS |
| | A 150 AMP MAIN BREAKER IN THIS PANEL. THE RISER DIAGRAM |
| | SHOWS A 200 AMP BREAKER ON 1/0 WIRE. CORRECT |
| | DISCREPANCIES. WPB FBC 107.2.1; NEC 240.4, |
| | 310.15(B)(16) |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 |
| | 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 5. RISER SHOWS PANEL HP AS EXISTING. AS THERE WAS A 125 |
| | AMP PANEL THERE PREVIOUSLY, THIS WOULD BE A NEW PANEL. |
| | PROVIDE CORRECTION. WPB FBC 107.2.1 |
| | 6. PROVIDE RISER DIAGRAM OF LANDLORD SERVICE INDICATING |
| | SIZE. NEC 215.5 |
| | 7. PROVIDE ACCURATE LOAD CALCULATION FOR LANDLORD |
| | SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM |
| | CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 8. RISER DIAGRAM SHOWS PANEL C AS A 100 AMP MAIN |
| | BREAKER PANEL. THE PANEL SCHEDULE SHOWS THAT THIS IS A |
| | 125 AMP MAIN BREAKER PANEL. THERE IS NOT INDICATION OF |
| | WIRE SIZE ON THE RISER DIAGRAM. PROVIDE CLARIFICATIONS |
| | AND CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC 215.5; |
| | 240.4, 310.15(B)(16) |
| | 9. PROVIDE CORRECTED LOAD CALCULATION FOR TRANSFORMER |
| | TLPC INCLUDING ALL LOADS CONNECTED. NEC 110.3, 220 |
| | 10. PROVIDE REVISED FLOOR PLAN SHOWING LOCATION OF |
| | PANEL C. WPB FBC 107.2.1 |
| | 11. PROVIDE GFCI PROTECTION FOR RECEPTACLE OUTLETS |
| | LOCATED WITHIN 6 FEET OF SINK. NEC 210.8 |
| | 12. PROVIDE NARRATIVE OF REVISIONS. THERE IS NO NEED TO |
| | SUBMIT SHEETS THAT ARE NOT BEING REVISED. ALL REVISIONS |
| | SHOULD BE CLOUDED ON PLAN. WPB FBC 107.2.1 |
| | 13. VALUE FOR WORK STATED ON REVISION APPLICATION |
| | APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE |
| | AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR |
| | FOR WORK DETAILED IN REVISION. WPB FBC 109.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |