| Plan Review Notes For Permit 19101624 |
| Permit Number |
19101624 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-16 13:04:57 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | GAS COMMENTS: | | | | | | 1. PROVIDE GAS RISER SHOWING LENGTH OF PIPE TYPE OF | | | PIPE SHOW SHUT OFF AND REQUIRED DRIP LEG SHUT OFF | | | SHOULD BR LOCKING TYPE. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. PROVIDE SIZING TABLE FROM FBC FG 2017 6TH EDITION. | | | | | | 3. PLACE NOTE ON PLAN SEPARATE PERMIT WILL BE REQUIRED | | | TO INSTALL GAS PIPING TO APPLIANCES. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 4. THE MAIN SHUT OFF VALVE SHALL BE LOCKABLE NOTE ON | | | PLAN. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|